I changed the supply air temperature high limit of the End X air handler from 60 to 65 degrees to give the program broader control of the chilled water valve. This will allow the program to throttle the chilled water rather than rely on heater coils for temperature control. This may create a small increase in the temperature trending while the P.I. loop adjusts.