Recovery from Sunday power outage

Jonathan, Erik, Dave.

IPMI end station HWS computers:

After the power outage both h1hws[ex,ey] computers' IPMI ports went off-line. I went to h1hwsex this afternoon and reset the computer into BIOS to check that its IPMI network setting were correct, they were. Back in the CUR Jonathan and myself went through the sw-ex-stk setting to ensure that switch2-port8 was on the ADMIN VLAN (yes), was up (yes) and could see somthing was connected (also yes).

I remembered that sometimes old server's BMC cards need a full power cycle to get going again, so at h1hwsey I powered it down and pulled both power cords for at least 30 secconds. When it powered back up I briefly went into BIOS to check the IPMI network settings (all good) and then booted. At this point the IPMI port for h1hwsey was operational again.

Back at h1hwsex I did the cords-out power cycle, which restored its IPMI as well.

I started the EX and EY HWS EPICS IOCs to get the EDC green again.

MY Weather Station

The power outage damaged the 24V Comtrol power suppy for both MY and EY. Erik found a spare PS in EE on Monday and got EY going. This afternoon I found a second spare PS in the MSR and got MY weather station going again.