MEDM
Confusingly we have been running with two separate copies of the vacuum overview MEDM.
CDS_OVERVIEW has been using /ligo/lho/h0/ve/medm/beckhoff/H0_VAC_SITE_OVERVIEW_CUSTOM.adl (not under any version control)
SITEMAP has been using /opt/rtcds/userapps/release/vacuum/h0/medm/Target/H0_VAC_SITE_OVERVIEW_CUSTOM.adl (under git version control)
It is the second one, which is git controlled, which should be used. I took the opportunity when fixing the MEDMs to remove use of the /ligo files and move CDS_OVERVIEW over to using the Target file.
Changes made to the site overview and committed to git (see attachment) are:
RED - HAM1 now only shows the new PT100_MOD2 gauge
YELLOW - IP24,IP25 have new names
PURPLE - text to show the local git working directory and git repo information
VACSTAT
I added the new HAM1 PT100_MOD2 gauge to VACSTAT last night. Initially I also removed the temporary H1 PT100B gauge, but then remembered this has channels in H1EPICS_VACSTAT.ini which caused EDC disconnects.
So for now VACSTAT has the new H0 PT100_MOD2 (not in DAQ) and the old H1 PT100B (in DAQ, but needs to be removed)
Trip levels were returned to pre-vent values.