We had a site wide power outage around 12:11 local time. Recovery of CDS has started.
I've turned the alarms system off, it was producing too much noise.
We are recovering front end models.
Jonathan, Erik, Richard, Fil, Patrick, EJ, TJ, RyanS, Dave:
CDS is recovered. CDSSDF showing WAPs are on, FMCSSTAT showing LVEA temp change.
Alarms are back on (currently no active alarms). I had to restart the locklossalert.service, it had gotten stuck.
BPA Dispatcher on duty said they had a breaker at the Benton substation open & reclose. At that time, they did not have a known cause for the breaker operation. Hanford fire called to report a fire off Route 4 by Energy Northwest near the 115KV BPA power lines. After discussions with the BPA dispatcher the bump on the line or breaker operation, may have been caused by a fault on the BPA 115KV line causing the fire. BPA was dispatching a line crew to investigate.