david.barker@LIGO.ORG - posted 11:40, Thursday 11 September 2025 - last comment - 15:13, Thursday 11 September 2025(86857)
Corner station dust monitors were recording high values overnight due to central pump offline

Tony, TJ, Dave:

After the power outage the CS dust monitors (Diode room, PSL enclosure, LVEA) started recording very large numbers (~6e+06 PCF). TJ quickly realized this was most probably a problem with the central pump and resolved that around 11am today.

2-day trend attached.

Images attached to this report
Comments related to this report
thomas.shaffer@LIGO.ORG - 15:13, Thursday 11 September 2025 (86864)PEM

The pump was running especially hot and the gauge showed no vacuum pressure. I turned off the pump and checked the hose connections. The filter for the bleed valve was loose, the bleed screw was full open, and one of the pump filters was very loose. after checking these I turned it back on and it immediately sucked to 20inHg. I trimmed it back to 19inHg and then rechecked a few hours later to confirm it had stayed at that pressue. The pump was also running much cooler at that point as well. 