Reports until 11:00, Friday 31 October 2025
H1 CDS
david.barker@LIGO.ORG - posted 11:00, Friday 31 October 2025 (87887)
FMCS LVEA/VEA fans off for a few minutes between 05:10 and 05:15 early Thursday morning

Eric, Dave:

Following up on the end station VEA temperature excursions yesterday morning, Eric noticed that the fan accelerometer channels looked strange just prior to that time.

The attached plot shows that most, but not all, of the LVEA/VEA fans were turned off for about 1min40sec each, with the turn off times not coincident, but over a period of several minutes.

FAN Turn Off Turn On Duration
EY 05:13:10 05:14:44 1min34
EX 05:12:32 05:14:13 1min41
MY 05:12:24 05:14:10 1min46
MX 05:11:41 05:13:19 1min38
LVEA-FAN1 05:12:28 05:14:10 1min42
LVEA-FAN2 05:12:31 05:14:12 1min40
LVEA-FAN3 05:10:57 05:12:30 1min33

LVEA-FAN4 is always zero. FAN5 and FAM6 have a signal but no change around this time.

Images attached to this report