Eric, Dave:
Following up on the end station VEA temperature excursions yesterday morning, Eric noticed that the fan accelerometer channels looked strange just prior to that time.
The attached plot shows that most, but not all, of the LVEA/VEA fans were turned off for about 1min40sec each, with the turn off times not coincident, but over a period of several minutes.
| FAN | Turn Off | Turn On | Duration |
| EY | 05:13:10 | 05:14:44 | 1min34 |
| EX | 05:12:32 | 05:14:13 | 1min41 |
| MY | 05:12:24 | 05:14:10 | 1min46 |
| MX | 05:11:41 | 05:13:19 | 1min38 |
| LVEA-FAN1 | 05:12:28 | 05:14:10 | 1min42 |
| LVEA-FAN2 | 05:12:31 | 05:14:12 | 1min40 |
| LVEA-FAN3 | 05:10:57 | 05:12:30 | 1min33 |
LVEA-FAN4 is always zero. FAN5 and FAM6 have a signal but no change around this time.