At 9:42p local I received a cell alert declaring a loss of chilled water supply at End X. After remotely logging into FMCS I observed that the lead chiller (1) was in alarm and the CH-1 supply temp was hovering around 54F. I've since toggled the lead lag, and manually forced chiller 2 and chilled water pump 2 on. Given the low outside air temps and the lack of temp demands that vent require, this should suffice until all return from the break where we can investigate further. T. Guidry