Using Vibration Sensors To Gauge Health Of HVAC Fans Site Famis 27735
No big changes here, got a few spikes that are likely DAQ restarts.
TCS Monthly Trends Famis 38836
There are some large spikes in this data on days where we have someDAQ restarts.
(Randy Thompson, Corey Gray)
In preparation for the upcoming Bigger BeamSplitter Suspension (BBSS) Installation at BSC2 in a few weeks (~midMarch), a new type of cleanroom infrastructure was needed too allow for more vertical space for the cartridge to be craned in/out of BSC2. Instead of using our standard large mobile cleanroom (which are used for HAM & BSC chamber work), a smaller clean space will be attached to the elevated work platform for BSC2. There will be a "cleanroom tent" on this platform (here's the platform [white] with 2-sets of 4 "tent poles") and a new array of (qty-4) HEPA Filters Fans (same type as the ones on top of the large mobile cleanrooms which blow down) will be on the side of this cleanroom tent to push air flow horizontally for this elevated workspace for the BBSS install.
Randy designed a unistrut framework for this 4-HEPA fan Array (weighs 377lbs). This morning this assembly was carefully craned into place on top of 3 unistrut brackets attached to the BSC work platform (in between BSC1 & BSC2). For added support, this afternoon, Randy added a "leg support" on both ends of this HEPA Filter Fan Array (here is a photo of one of these legs that is in the Beer Garden).
Note, the HEPA bank wall is intended to be moved from platform to platform when needed, so any interference of other areas due to them is somewhat temporary.
Fri Jan 30 10:07:58 2026 INFO: Fill completed in 7min 54secs
TITLE: 01/30 Day Shift: 1530-0030 UTC (0730-1630 PST), all times posted in UTC
STATE of H1: Planned Engineering
OUTGOING OPERATOR: None
CURRENT ENVIRONMENT:
SEI_ENV state: MAINTENANCE
Wind: 3mph Gusts, 1mph 3min avg
Primary useism: 0.04 μm/s
Secondary useism: 0.40 μm/s
QUICK SUMMARY:
LVEA is LASER HAZARD with HAM1 & HAM7 still open for in chamber work.
Potential HAM7 work:
Tweak Alignment from cable Rubbing, OBO & TF
Potential HAM1 work:
Align Path out
IOT2L Beam profile measurement at 100 mW
Replace JM1/JM3 fixed mirrors with HTTS
Lock MC with HAM1 in air
Bifricate LVEA HAM1/South Bay/Work at Height all Laser Haz, rest of LVEA Laser Safe
This morning Rahul took a transfer function of the OPO suspension and found that adding a zip tie to the new connector didn't help the transfer function, which is still similar to 88921. We decided with Jeff to live with this as it is, and we spent the rest of the day working on resolving the clipping through the VIP introduced by alignment shifts that happened as we were addressing the cables.
We moved A:M3 enough that we no longer see evidence of clipping in the SFI1 both passes, we measure 0.96mW out of the OPO and about the same power in transmission from SFI1 on the the return from the filter cavity. We then saw that the beam was clipping in SFI2, and adjusted B:M1 until we were measuring about 0.88- 0.9mW after SFI2, but we had clipping on the aperture attached to B:L2. We had nearly lost the beam to SQZT7 by this time, so we spent some time restoring that by adjusting pitch on B:M3 and yaw on B:M4 (with the platform unlocked it is difficult to adjust pitch on the tough pitch knob for B:M4). This brought us to a point where we can see 0.7 counts on the OPO IR PD on SQZT7.
At the end of the day, we were still seeing loss at B:L2, where the beam was only about 0.82mW. We also need to restore the alignment onto the irises on SQZT7.
We will need to readjust the alignment onto the filter cavity QPDs before we close the chamber.
Power measured this morning in HAM7,
0.95mW out of OPO
0.92mW out of SFI2
0.83mW ou of B L2
0.83mW on table (and looks centered on both the iris on the able).
We are somehow clipping on the lens (placed after the SFI2), we might move it mechanically since adjusting the beam using mirror is not helping.
Details to follow.
EOM tuning results
It's worth noting that we haven't done any tuning after EOM was transported from the lab to HAM1. Frequencies changed a bit but nothing to worry about.
Below is a table of the dip frequencies and S11 coefficients when the EOM was placed in its final location. They aren't bad, 9 and 45 are as good as anybody can do.
(We also measured them when EOM was placed at the edge of the table, there were measurable differences but nothing disastrous.)
| nominal / measured center frequency [MHz] | measured S11 coeff [dB] at nominal / center frequency |
| 9.100230 / 9.1015282 | -21.96 / -22.29 |
| 24.078360 / 24.074976 | -25.84 / -26.74 |
| 45.501139 / 45.499614 | -23.19 / -23.15 |
| 118.30299 / 118.294670 | -25.29 / -26.0 |
Connection
FieldFox network analyzer was connected to the modulation patch panel at the bottom of PSL rack (which is kind of hard to find, see the first picture). Back of that panel is connected to the in-air cable that runs all the way to the vacuum feedthrough on HAM1.
By connecting 50 Ohm terminator to each in-vac cable, we confirmed from FieldFox that ISC_RF5-B1, B2, B3 and B4 correspond to 9, 45, 118 and 24MHz as specified in D1900511-v12 page 43 and 24.
Before connecting the cables to the EOM, we performed S11 calibration by connecting a short plug, 50 Ohm plug and nothing to the SMA connector of in-vac cables via class B SMA elbow.
After the EOM was relocated to its final location, RF sources were connected to the front of the patch panel.
RF levels of the signals directly coming from the 118MHz and 24MHz RF patch panel were: 10.76dBm for 118MHz, 14.2dBm for 24MHz according to FieldFox.
45MHz and 9MHz come from the EOM driver and I didn't bother to measure the power.
Other things
In three_persons_untangling.jpg, Jennie, Jason and Elena (left to right) are untangling JAC EOM cables together.
About the cable strain relief posts:
The four SMA cables were connected to the SMA elbow connectors on the EOM. The strain relief posts appear to be designed such that each cable is sandwiched between the two viton pieces, with one screw above and one screw below. I was a bit confused about how exactly to use the screws with hex nuts attached. I instead used the third bottom screw to loosen to slide the cable in, and then tighten. It was helpful to have someone else pinch the viton at the top while I tightened the screw. This is how it looks.
The two cables on the right hand side of the EOM mount feed straight through the strain relief into the SMA connection, this is fine. However, the placement of the post on the left hand side is a bit short of where the SMA connections are, so the cable bends a bit to make it through the strain relief post and go to the connector. This is tricky because the SMA cable is also very stiff. I don't know if this is a problem. I took several pictures of how this looks just in case. You can see how one side is straight and the other side is "S" shaped through here.
There are two more angled shots of the EOM in its place on the table.
About EOM placement:
Jason and I lifted and placed the EOM carefully together while Jennie held the cables. We roughly dog-clamped the cables to the table for now. Jason fine-tuned the EOM alignment by lining up the mechanical mount to holes on the table.
Overall, not bad for placement. We opened the light pipe after placement, locked the JAC and saw the beam go in to the EOM and then come out of the EOM on the other side!
To confirm, we used the thorlabs power meter to check. We measured about 82-84 mW before the EOM, and then 79-80 mW coming out of the EOM.
Further alignment work:
We proceeded to try to realign the beam from JM2 to JM3, given the significant deflection of the beam due to the EOM crystal. There are two irises between the mirrors to guide the alignment. Jason found it very tricky to align the beam to both. During the process, JM2 was knocked over and now has some scratching and cracks near the edge of the mirror. It is fine to use it for alignment now, but the mirror will need to be replaced. The team is working on finding a spare now.
EPO Tagged.
TITLE: 01/30 Day Shift: 1530-0030 UTC (0730-1630 PST), all times posted in UTC
STATE of H1: Planned Engineering
INCOMING OPERATOR: None
SHIFT SUMMARY: EOM is in!! Still some work to be done for HAM1 and HAM7. LVEA IS LASER HAZARD
LOG:
| Start Time | System | Name | Location | Lazer_Haz | Task | Time End |
|---|---|---|---|---|---|---|
| 15:44 | Corey | LVEA | YES | Running HAM1 cable brackets out | 15:52 | |
| 16:18 | FAC | Kim, Nellie | LVEA | YES | Tech clean (Nellie out 16:30) | 17:48 |
| 16:22 | FAC | Randy | LVEA | YES | Measuring on BSC2 platform | 16:52 |
| 16:29 | FAC | Nelllie | EY, MY | n | Tech clean | 17:39 |
| 17:28 | JAC | Keita | OptLab/LVEA | n | EOM work | 19:35 |
| 17:31 | SQZ | Rahul, Sheila | LVEA | YES | HAM7 alignment | 19:59 |
| 17:34 | FAC | Randy | LVEA | YES | BSC2 platform work | 19:37 |
| 17:38 | VAC | Jordan | MY | n | Looking for parts | 17:56 |
| 17:51 | JAC | Betsy, RyanS | LVEA | YES | Moving IOT1 away from chamber (RyanS out 19:35) | 19:43 |
| 17:57 | SPI | Jim | OptLab | n | SPI work | 19:11 |
| 18:01 | EE | Fil, Marc | LVEA | YES | Pulling cables | 19:14 |
| 18:03 | JAC | Elenna | OptLab/LVEA | n | EOM work | 19:35 |
| 18:04 | FAC | Kim | LVEA | YES | Tech clean | 18:24 |
| 18:10 | JAC | Masayuki | LVEA | YES | EOM | 19:35 |
| 20:30 | FAC | Randy | LVEA | YES | BSC2 platform work | 22:49 |
| 20:43 | EE | Fil | LVEA | YES | Cabling for BHD | 21:56 |
| 20:43 | JAC | Keita | LVEA | YES | EOM installation work | 20:58 |
| 20:49 | JAC/VAC | Jason, Jennie, Jordan, Keita | LVEA | YES | Replacing septum cover (Jordan out 21:13) | ongoing |
| 21:02 | EE | Marc | LVEA | YES | Helping with JAC | 21:21 |
| 21:10 | JAC | Elenna | LVEA | YES | JAC | ongoing |
| 21:26 | SQZ | Sheila, Rahul | LVEA | YES | HAM7 aligning | 00:01 |
| 22:25 | EE | Marc, Yuri | LVEA | YES | Looking around | 23:25 |
| 22:39 | BHD | Betsy, Jenne | OptLab | n | BHD things | 23:54 |
| 23:19 | JAC | Masayuki | LVEA | YES | JAC work | ongoing |
| 23:27 | Richard | LVEA | YES | Checking in on everything and being nice to people | 22:57 | |
| 00:21 | FIT | Matt | YARM | n | Running | ongoing |
Thu Jan 29 10:07:23 2026 INFO: Fill completed in 7min 20secs
Closes FAMIS#39852, last checked 88845
Corner Station Fans (attachment1)
- MR FAN1_170 has been relatively loud since it was turned on on Tuesday.
- All other fans are looking normal and within range.
Outbuilding Fans (attachment2)
- MY FAN1_270_1 is quite noisy, but since it's at the midstation I think that's okay
- All other fans are looking normal and are within range.
Sheila, Jeff, Rahul
Yesterday afternoon we moved around two more cables on the OPO (see picture attached for reference). For the first cable (marked by circle) we lifted the cable connector from the OPO and attached it to the nearby pillar using a PEEK tie. For the second cable (marked by arrows in my picture) I provided more relief to it.
This morning I took transfer function measurements for Y dof (0.02Hz bw and 5 averages, with Yaw dof. un-damped and other dof. being damped during the measurement) - see screenshot attached below. I don't see any improvement (in frequencies splitting) - red trace is the latest measurement and blue is the previous one taken by Jeff two days ago.
Yesterday Rahul and I went to HAM7 and adjusted A:M3 in the negative pitch direction to relive the saturation of ZM1 noted in 88939. This was partially sucsesful, after the shift the beam was no longer clipping on the SQZT7 periscope without offsets on ZM1, but it was a little low in pitch on the first iris and the power on the OPO IR trans PD was 0.4 rather than 0.6 counts. With the power meter we can see that there is still clipping between the input to SFI1 and the return beam from the filter cavity out of SFI1.
Rahul adjusted the cables a bit, adding more slack to the one for the OPO temperature controler (before photo shows this as the lighter colored cable with the S routing on the nearby pillar). The beam was still After that the PSL FSS would not lock, preventing us from dither locking the OPO.
Rahul moved the connector for the new translation stage from the lid of the OPO and zip tied it to the pillar on the rear blade spring.
Oli and Jeff are looking at suspension transfer functions right now. I was able to improve the power on the PD from the control room by pitching ZM1 + 400 urad and yawing +500 urad, but there is still not as much light as we expect on SQZT7 IR PD, so we will have to continue this in laser hazard today.
We've assembled the whole EOM assembly including the pivot base/plate assy and the strain relief post and confirmed that the EOM face/side/bottom plates are isolated from the pivot base/plate.
We've tuned the EOM such that S11 parameter at the modulation frequencies are all within 1dB of the bottom of the dip.
We still saw that the frequency shifted for 118 and 45MHz when we tapped the EOM body around, even though there was no appreciable change in 24 and 9MHz. Each jump was small, like 5kHz or 10kHz or nothing sometimes, but they jumped. Surprisingly, at least for 118MHz peak, after the frequency jumped in one direction due to my tapping on the side plate (e.g. the input side), I tapped the other side plate (e.g. the output side plate) and the frequency jumped back into the opposite direction. This was very consistent.
This means that my expectation was wrong. An expectation that somehow something (like coil wires) is caught by something else (like the core by the friction), and that tapping things will release these "something"s into lower potential state and that eventually they all settle.
Realizing this, we stopped tapping, we just tuned as good as we could and stopped.
Tools and parts were wrapped and bagged. EOM assy was wrapped in a foil. These things will be transported to HAM1 tomorrow.
In the first two attachment, Elenna is tuning the trickiest frequency (118MHz).
Following pictures show the fully assembled unit from the back (+Y), input (-X), output (+X) and front (-Y). In front.jpg, note that I'm only using one washer for the low profile 10-32 socket head cap screw. I used to use two, but the screw still stuck out just enough to make things tedious and inconvenient when lowering the pivot plate over the pivot base. Though the screw is 0.5" long and not the initially specified 10-32 x 0.375", with one washer it seems to work.
Next, look at one 1/4-20 screw below the above mentioned 10-32 in caution.jpg. When tightening/loosening that screw, don't use a T-handle wrench unless it's a ball end tool, because you WILL damage the SMA connector thread. Even if you use an L-shaped tool, if you don't pay attention you can damage it. Be careful.
Last picture showcases a happy mood in the optics lab after the successful day.
We modernized the measurement apparatus and used FieldFox (Agilent/Keysight's handheld network analyzer) instead of 4396B. This was really convenient and helpful because one person could hold the analyzer at a convenient position/angle for the other who was turning the trim cap.
Also it has a splitter and a directional coupler built in so there's no need to connect any such external devices, it's just the analyzer, a cable and the EOM. (But of course you still have to calibrate with short/open/load like in 4396B, see alog 88887.
EPO tagged.
Just want to add some notes:
Jennie W, Jason O
Jason and I added four beam dumps - two before we turned the power up, two after.
There were no beams leaving the table at 100mW but we dumped two beams going towards the PSL septum plate (one was transmission through JM1).
Jason saw one leaving the table after we were at one watt so this and the transmission throuhg JM3 + JM2 are now dumped.
PSL power into HAM1 has been returned to ~100mW and the PSL rotation stage is de-energized and locked out once again.
Pictures of the beam dump positions are attached.
BD one: BD for beam reflected towards PSL from JAC (-x direction).
BD two: beam transmitted through temporary JM3, BD (right one in photo) at edge of table nest to JM1 tip-tilt (in its temporary position in bottom right of photo).
BD three: BD in bottom of picture added for beam transmitted through temporary JM1.
Photo of both BD 1 and 3 zoomed out.
BD four: BD on -x side of table (towards HAM2) catching beam transmitted through JM2, shown in mid-left of photo.