rahul.kumar@LIGO.ORG - posted 13:35, Tuesday 13 January 2026 - last comment - 16:22, Tuesday 13 January 2026(88748)
HAM1 update - added some lenses and mirrors for JAC

Masayuki, Jennie, Rahul

Given below are the list of lenses and mirrors I have placed on the ISI table and roughly positioned (without the beam for now) them as per following drawings  - D2500344 and D0901821.

Lenses - L1, L2 and L3: Masayuki confirmed from the vendor that the arrow mark on the lens point towards the convex side. For lens L1, arrow is pointing against the PEEK ring (in the lens holder). For Lens L2 and L3 the arrow is pointing towards the PEEK ring. The PEEK ring for all three lens are facing towards the HAM2 chamber. In other words, curved surface of L1 is facing towards the PSL and for L2-3 towards HAM2.

I re-cleaned L1 lens after finding some dust particles on the curved surface, post cleaning the lens looked better.

Reflecting mirrors - JAC-RM1, JAC-RM2, JM2 and M3.

Masayuki and I also added a temporary Siskyou mount acting as JM3 (for Tip Tilt, just like JM1). We will replace both of them with the Tip Tilt next week.

Next, we proceed with aligning/pointing the above optics with the beam. L1 and JM2 are already decently pointing (although without a locked JAC) towards JM3.

Comments related to this report
rahul.kumar@LIGO.ORG - 16:22, Tuesday 13 January 2026 (88749)

Pictures attched from HAM1 chamber.

Images attached to this comment
H1 SUS (CDS, SEI)
jeffrey.kissel@LIGO.ORG - posted 08:45, Tuesday 13 January 2026 - last comment - 11:59, Thursday 22 January 2026(88745)
H1SUSB123 and H1SUSH34 SUS and SEI Systems prepped in SAFE for Conversion to SUSB13 and SUSH34
J. Kissel
ECR E2500296, E2400409
WP 12962

D2300401 (for susb13) and D2300383 (for susb2h34)

We begin the major upgrade of the H1SUSB123 and H1SUSH34 SUS and SEI Systems converting them to SUSB13 and SUSH34 a la G2301306 today. We're focusing on upgrading the DACs in the IO chassis () and all the downstream surrounding impact of that  analog electronics This will take down the following computers, and they will be resurrected with new names as follows:
    FORMER NAME           FORMER SUS              NEW NAME           NEW SUS
    h1susb123             ITMX, ITMY, BS          h1susb13           ITMX, ITMY
    h1sush34              MC2, PR2, SR2           h1susb2h34         BS, MC2, PR2, SR2, LO1, LO2
    h1susauxb123          ITMX, ITMY, BS          h1susauxb13        ITMX, ITMY
    h1susauxh34           MC2, PR2, SR2           h1susauxb2h34      BS, MC2, PR2, SR2, LO1, LO2

As such, I've 
    - brought the ITMX, ITMY, BS, HAM3, and HAM4 SEI systems to ISI_DAMPED_HEPI_OFFLINE (so we don't risk any "hard" trips of HEPI during all this).
    - brought all impacted SUS gaurdians to AUTO mode, then to the SAFE state
    - Increased the bypass time on all impacted software watchdogs to bypass time to a large number (90000000 secs), and hit BYPASS
Comments related to this report
marc.pirello@LIGO.ORG - 16:20, Tuesday 13 January 2026 (88752)

Updated timing cards on newly named SUSB13, SUSB13 AUX, SUSB2H34, SUSB2H34 AUX, formerly known as SUSB123, SUSB123 AUX, SUSH34 and SUSH34 AUX.

Timing FPGA Version 1589

marc.pirello@LIGO.ORG - 11:59, Thursday 22 January 2026 (88849)

While we were modifying the power systems in the SUS racks, the AA chassis S1202818 lost its negative voltage rail.  We pulled the chassis and replaced the power board.  This chassis was placed directly back into service.

M. Pirello, O. Patane, J. Kissel

LHO General
ryan.short@LIGO.ORG - posted 08:22, Tuesday 13 January 2026 (88744)
Ops Day Shift Start

TITLE: 01/13 Day Shift: 1530-0030 UTC (0730-1630 PST), all times posted in UTC
STATE of H1: Planned Engineering
OUTGOING OPERATOR: None
CURRENT ENVIRONMENT:
    SEI_ENV state: MAINTENANCE
    Wind: 5mph Gusts, 3mph 3min avg
    Primary useism: 0.02 μm/s
    Secondary useism: 0.49 μm/s 
QUICK SUMMARY: CDS upgrades this morning; moving SUS in BSC2 over into the sush34 model and upgrading to LIGO DACs. JAC installation and HAM7 beam alignment will continue as well today.

H1 CDS
erik.vonreis@LIGO.ORG - posted 06:52, Tuesday 13 January 2026 (88743)
Workstations updated

Workstations were updated and rebooted.  OS packages were updated.  Conda packages were not updated.

H1 CDS
david.barker@LIGO.ORG - posted 16:46, Monday 12 January 2026 - last comment - 16:59, Monday 12 January 2026(88741)
h1lsc model restart, DAQ restart, EDC move, add JAC_LOCK guardian channels to EDC.

Daniel, Ryan S, Erik, Jonathan, Dave

In preparation to tomorrow's work on h1susauxb123 we decided to move the EDC from here to h1susauxh56. We did this at the same time the DAQ was being restarted for:

1 Daniel's new h1lsc model

2 Adding Ryan's JAC_LOCK guardian node to EDC

The EDC move had a few configuration issues which were quickly resolved. There were no issues with the h1lsc restart.

 

Comments related to this report
david.barker@LIGO.ORG - 16:59, Monday 12 January 2026 (88742)

Mon12Jan2026
LOC TIME HOSTNAME     MODEL/REBOOT
14:51:52 h1lsc0       h1lsc       <<< Daniel's latest model


14:56:29 h1susauxh56 h1edc[DAQ] <<< EDC move to susauxh56
15:06:45 h1susauxh56 h1edc[DAQ]


15:11:30 h1daqgds1    [DAQ] <<< DAQ restarts
15:15:34 h1daqdc1     [DAQ]
15:15:41 h1daqdc1     [DAQ]
15:15:47 h1daqfw1     [DAQ]
15:15:47 h1daqnds1    [DAQ]
15:15:47 h1daqtw1     [DAQ]
15:16:32 h1daqgds1    [DAQ] 
15:25:15 h1daqnds0    [DAQ]
15:25:26 h1daqfw0     [DAQ]
15:25:27 h1daqgds0    [DAQ]
15:25:29 h1daqfw0     [DAQ]
15:25:29 h1daqnds0    [DAQ]
15:25:29 h1daqtw0     [DAQ]
 

LHO General
ryan.short@LIGO.ORG - posted 16:31, Monday 12 January 2026 (88740)
Ops Day Shift Summary

TITLE: 01/13 Day Shift: 1530-0030 UTC (0730-1630 PST), all times posted in UTC
STATE of H1: Planned Engineering
INCOMING OPERATOR: None
SHIFT SUMMARY: Laser safe in the LVEA this morning for some craning and cabling, both in-chamber and out, but now back to laser HAZARD for more JAC installation and SQZ beam alignment this afternoon.
LOG:

Start Time System Name Location Lazer_Haz Task Time End
---- SAF HAZARD LVEA YES LVEA is Laser HAZARD Ongoing
15:15 FAC Randy, Eric LVEA N Craning 16:45
15:58 FAC Kim, Nellie LVEA N Garb & garbage 16:28
16:14 SAF Richard LVEA N Grabbing keys 16:17
16:46 FAC Kim, Nellie LVEA N Technical cleaning 17:42
16:50 CDS Marc, Fil LVEA N Checking panel placement 18:06
16:51 CAL Tony PCal Lab Local Start measurement 17:42
16:59 FAC Randy LVEA N Craning 17:24
17:12 VAC Gerardo EX N Troubleshoot ion pump 17:37
17:28 SQZ Sheila, Jim LVEA N HAM7 cabling 19:24
17:34 JAC Jennie, Rahul LVEA N JAC optics 18:06
17:39 PEM RyanC LVEA N Checking dust monitors 18:18
18:06 CDS Fil, Marc LVEA N Cable pulling input arm 20:17
18:11 JAC Jennie, Rahul LVEA N JAC optics 19:11
18:28 FAC Randy LVEA N Walkabout 18:40
18:33 PEM RyanC EY, EX N Checking dust monitors 19:37
18:40 FAC Randy EY N Dropping off equipment 20:31
18:43 FAC Kim, Nellie LVEA N Technical cleaning 19:31
18:58 FAC Tyler LVEA, MX, MY, EX, EY N 3IFO checks 20:58
19:31 FAC Kim MX N Technical cleaning 20:04
19:35 VAC Gerardo LVEA N Looking for parts 19:48
19:58 SQZ Sheila, Jim LVEA N HAM7 cabling 20:29
20:37 SAF RyanC LVEA Y Laser HAZARD transition 20:53
21:04 JAC Jennie LVEA - Turning on JAC HV 21:07
21:09 FAC Richard, Tyler, contractors LVEA - Electrical checks near HAM1 21:53
22:11 VAC Gerardo, Travis EX N Replacing AIP controller 23:00
22:14 SQZ Sheila LVEA Y Turning on SQZ laser, opening viewport 22:26
22:44 JAC Jennie, Masayuki, Rahul LVEA Y JAC installation Ongoing
22:52 CAL Jeff CER - Pictures of racks 22:59
22:56 SQZ Sheila, Kar Meng LVEA Y HAM7 SQZ beam alignment 00:04
22:59 CAL Tony PCal Lab Local Check measurement 00:16
23:13 JAC Betsy LVEA Y JAC installation 00:13
23:34 FAC Tyler LVEA - Checks 23:40
23:51 SQZ Elenna LVEA Y HAM7 SQZ beam alignment 00:04
LHO VE (VE)
gerardo.moreno@LIGO.ORG - posted 14:02, Monday 12 January 2026 - last comment - 14:51, Tuesday 13 January 2026(88739)
X2-8 Ion Pump Out of Service

(Travis, Dave, Gerardo)

Dave noted and reported a rise on vacuum pressure at X-End.  Since, Travis and I were in the control room, we quickly determined that the controller for X2-8 ion pump was not working.  I drove down and found the high voltage disabled/off at the controller, and on on the screen the following note:"An excessive arcing condition has been detected (Error10)".  No guidance found on manual, snapped a photo to submit later to vendor.  I restarted the system and the HV started, controller hummed and crackled and was only able to get up to 600 Volts, all while making noise, and one point some funny smell came out of the inside of the controller, HV was disabled, time to replace the unit.

Images attached to this report
Comments related to this report
gerardo.moreno@LIGO.ORG - 14:51, Tuesday 13 January 2026 (88750)VE

(Travis, Gerardo, Richard)

Controller remains off, and high voltage cable is disconnected at both ends, ion pump and controller.

We found a controller for this particular application, and replaced the "old" controller but with similar results, minus the noise.  The controller was only able able to get up to 500 volts and no more.  We turned it off and disconnected the high voltage cable.

I later visited the cable and ion pump to measured them for shorts.  I disconnected the cable from the ion pump, then probed the connector at the controller side, center pin to the shell read 0.808 kOhm, I also probed the center connector to other parts of the cable, but no continuity was read for all cases, including to the conduit.  The ion pump itself was probed for shorts and none was found, at the ion pump connector the center pin was probed to the ion pump body and no continuity was measured.  To compare cables, I measured a "new" cable that we have that is probably half the length of the one in use, no continuity was measured.

I'll wait for the EE guys to have a free moment for them to test the cable.

Images attached to this comment
H1 PEM
ryan.crouch@LIGO.ORG - posted 13:09, Monday 12 January 2026 (88737)
Quarterly Dust Monitor testing FAMIS

Closes FAMIS#27662, previous check in alog84918. No new issues with any dust monitors.

**PSL Anteroom and Laser Room will be done at a later date when going in there is required for other tasks by Ryan Short.**

For the CS dust monitors.


LVEA: 

HAM1 / LVEA5: On the +Y side of the HAM1 CR. Passed the zero count on the first round, and the flow was 2.8. PASS

HAM1: An additional spare DM on the -Y side of the HAM1 CR. Passed the zero count on the first round, the flow was a bit high at 3.0 so I adjusted it down to 2.8. PASS

HAM7 / LVEA6: Passed the zero count on the first round, and the flow was 2.8. PASS

Biergarten / LVEA10: Passed the zero count on the first round, and the flow was 2.8. PASS

DR: This DM was frozen when I got to it. Passed the zero count on the second round (first round had 2 cts of 0.3 um), and the flow was 2.8. PASS

Optics Lab: Passed the zero count on the first round, and the flow was 2.8. PASS

VPW: Passed the zero count on the second round (first round had 1 ct of 0.3 um), and the flow was 2.8. PASS

CER:

All the old grey HHPC handheld dust monitors in various states of degradation, none of them can take a full sample on power or battery without dying. I've removed the last one of this model I found in the CER and added it to collection of the other broken ones.

I tested the last spare GT521s left in the CER as well which I had borrowed from the FCES (s/n R16420). It passed the zero count test on the 2nd round (first round had 1 ct of 0.3 um) and the flow is 2.8. PASS

For the OUT building dust monitors.


EY: Passed the zero count on the second round (first round had 1 cts of 0.3 um), and the flow was 2.8. PASS

EX: Passed the zero count on the second round (first round had 1 cts of 0.3 um), the flow was a little low 2.65 so I went to adjust the pump in the mechanical room. These new vacuum pumps' adjustment knob seem touchier than the old one. It was at 19.5 inHg, I adjusted it up to 20 but it would stay at 20, it kept slowing increasing in pressure. I watched it slowly build up to almost 22 after I adjusted it up slightly to 20. I ended up bringing it back down to as close as I could get to where it was. I ended up around 19.8 inHg which brought the DM flow back to a little over 2.7, within the 5% margin of error. PASS

LHO VE
david.barker@LIGO.ORG - posted 10:56, Monday 12 January 2026 (88738)
Mon CP1 Fill

Mon Jan 12 10:05:34 2026 INFO: Fill completed in 5min 30secs

 

Images attached to this report
LHO General (SEI)
ryan.short@LIGO.ORG - posted 07:45, Monday 12 January 2026 (88735)
Ops Day Shift Start

TITLE: 01/12 Day Shift: 1530-0030 UTC (0730-1630 PST), all times posted in UTC
STATE of H1: Planned Engineering
OUTGOING OPERATOR: None
CURRENT ENVIRONMENT:
    SEI_ENV state: MAINTENANCE
    Wind: 8mph Gusts, 4mph 3min avg
    Primary useism: 0.03 μm/s
    Secondary useism: 0.59 μm/s 
QUICK SUMMARY: JAC install and HAM7 alignment will continue today after craning finishes in the LVEA and it's transitioned back to laser hazard.

[Tagging SEI] The ETMX CPS glitched over the weekend, tripping both stages of the ISI, and I am unable to reset it without it tripping again immediately. Since ETMX isn't crucial for planned work today, I'll wait until Jim gets in and consult with him.

LHO VE
david.barker@LIGO.ORG - posted 11:04, Sunday 11 January 2026 - last comment - 08:11, Monday 12 January 2026(88734)
Sun CP1 Fill, 10:00 fill did not run, manually ran a fill at 10:50

Regularly scheduled fill at 10:00 did not run because both thermocouples were above the +30C nominal max limit [31C, 34C] presumably due to icing around the TC and/or Ref Junction.

Sun Jan 11 10:00:00 2026 ALARM: Abort run, Both Thermocouples BAD

I made a temporary change to the configuration to increase the nonimal TC-MAX to +40C and scheduled at 10:50 run.

Sun Jan 11 10:58:34 2026 INFO: Fill completed in 8min 30secs

This appears to be a good fill. The settings will be restored to nominal for tomorrow's fill.

 

Images attached to this report
Comments related to this report
david.barker@LIGO.ORG - 08:11, Monday 12 January 2026 (88736)

Monday's fill will also run with the elevated NOM_MAX=40C settings. Currently TC are [31C,34C].

LHO VE
david.barker@LIGO.ORG - posted 10:53, Saturday 10 January 2026 (88733)
Sat CP1 Fill

Sat Jan 10 10:09:50 2026 INFO: Fill completed in 9min 47secs

 

Images attached to this report
H1 IOO (IOO)
masayuki.nakano@LIGO.ORG - posted 20:56, Friday 09 January 2026 - last comment - 11:22, Tuesday 13 January 2026(88731)
JAC working log 1/8-9

[Jason, Jennie, Betsy, Keita, Sophie, Masayuki]

Initial alignment (1/8)

 


JAC wiring (1/8)


Wiring confirmation (1/9)


Optics preparation (1/9)

 

Images attached to this report
Comments related to this report
keita.kawabe@LIGO.ORG - 21:59, Friday 09 January 2026 (88732)

Mirrors inspected:

Mirror status was found what was done
M2 Not ready in a lens container with foam sponge after the first cotnact was removed, which is a bad idea. Many dust particles after taking it out of the box. Painted first contact.
M3 Ready Was in the chamber, first contact still on. Removed FC while using top gun. A big dust particle in the back surface, couldn't remove with further top gun, but that's OK.
RM3 Not ready Was in the chamber, first contact still on. Removed FC while using top gun. One dust particle close to the center, couldn't remove. Painted FC.

M3 assy is in the chamber (but is still at the edge of the ISI).

M2 and RM3 optics are stored outside of the chamber.

Lens First Contact problem:

All of the lenses had at least one surface where the first contact was incredibly strongly attached. Simple pulling of the mesh won't do anything even with serious force. We wiggled the mesh in multiple directions with enormous force and the mesh started separating from the FC. Will discuss with Betsy on Monday. All of these are stored outside of the chamber.

L1 FC remains on one surface. Painted FC on top of the existing layer over the mesh. Will see if it makes the FC loose.
L2 FC remains on both surfaces.
L3 FC remains on one surface.

2" Lens Post issue:

All pieces of 8-32 variant of D1000968-v3 were manufactured incorrectly, they have 8-32 bottom screw holes so cannot be mounted on the standard ISC baseplate.

To make them usable, the bottom hole should be widened and re-tapped for 1/4-20 though there's no urgency because we were able to use the original 1/4-20 version. (It seems that this variant was requested on a wrong assumption that Siskiyou lens mount only accepts 8-32. In reality the lens mount has two screw holes, one for 8-32 and the other for 1/4-20, so this variant isn't really needed.)

corey.gray@LIGO.ORG - 11:22, Tuesday 13 January 2026 (88747)EPO

Tagging for EPO photos

H1 IOO (IOO)
masayuki.nakano@LIGO.ORG - posted 09:13, Thursday 08 January 2026 - last comment - 11:21, Tuesday 13 January 2026(88713)
JAC in HAM1

[Jason, Rahul, Jennie, Betsy, Masayuki]

Summary

JM1 was swapped from a tip-tilt suspension to a fixed Siskiyou mount to improve beam stability for alignment, profiling, and JAC control. Mode matching to the JAC was measured using a beam profiler, yielding <1.5% mismatch in both axes, well within the current requirement. The JAC pedestal and body were installed in HAM1, and initial beam injection showed clear HoM resonances at the transmission port. One discrepancy in body mode damper mounting holes was identified and will be tracked via FRS.

Details

 

Images attached to this report
Comments related to this report
jennifer.wright@LIGO.ORG - 09:43, Thursday 08 January 2026 (88715)

I attached the photos of the readout from the nanoscan with the first one being the beam size at the front of the rail, second labelled zero is at zero of the rail, and the others are labelled with the position on the rail in mm.

Images attached to this comment
corey.gray@LIGO.ORG - 11:21, Tuesday 13 January 2026 (88746)EPO

Tagging for EPO photos

Displaying reports 2761-2780 of 88978.Go to page Start 135 136 137 138 139 140 141 142 143 End