edgard.bonilla@LIGO.ORG - posted 18:13, Friday 26 September 2025 (87166)
M1, M2, and M3 OSEM calibration for SRM

I used Oli's SRM OSEM calibration measurments from [LHO: 87112] to get the absolute calibration of the SRM OSEMs. I only bothered with the ALIGNED position because that's is the official set of measurements for calibration.

I also used a new, quasi-automated version of the calibration script used for the PR3 and SR3 suspensions. The script fits the 6-15 Hz data directly to 1 [OSEM m]/[GS13 m], no additional modelling is involved in the calibration.
The script's information, coordinates, and instructions will be the subject of a later logpost.

The results of the calibration are a mouthful because we are now doing M1, M2, and M3 all simultaneously.
The TL;DR is that the M1 OSEM calibrations seemed off by factors of 1.8 or so, larger than the SR3/PR3 averages, but not unexpected. 
The M2 and M3 absolute calibrations were surprisingly good. They were all high from the GS13 measurments by a factor of 10% or so, which leads me to believe this is likely not a coincidence and someone may have previously done an absolute calibration of the SRM M2/M3 OSEMs. I would love to confirm these suspicions, but such work may be lost to time.

See the PDFs attached for the before and after calibration for all three stages.

Here is the full calibration script output:

___________________________________________

OSEM calibration of H1:SUS-SRM
Frequency range for calibration: 6 to 15 Hz
Stages to be calibrated: ['M1' 'M2' 'M3']
Measurement date: 2025-09-23_1830 (UTC).


%%%%%%%%%%%%
Stage: M1
%%%%%%%%%%%%

The suggested (calibrated) M1 OSEMINF gains are
(new T1) = 1.756 * (old T1) = 1.958
(new T2) = 1.806 * (old T2) = 2.127
(new T3) = 1.761 * (old T3) = 1.842
(new LF) = 1.945 * (old LF) = 2.102
(new RT) = 1.593 * (old RT) = 1.819
(new SD) = 1.525 * (old SD) = 1.794

To compensate for the OSEM gain changes, we estimate that the H1:SUS-SRM_M1_DAMP loops must be changed by factors of:
L gain = 0.571 * (old L gain)
T gain = 0.656 * (old T gain)
V gain = 0.565 * (old V gain)
R gain = 0.565 * (old R gain)
P gain = 0.561 * (old P gain)
Y gain = 0.571 * (old Y gain)

The calibration will change the apparent alignment of the suspension as seen by the M1 OSEMs
NOTE: The actual alignment of the suspension will NOT change as a result of the calibration process

The changes are computed as (osem2eul) * gain * pinv(osem2eul).
Using the alignments from 2025-09-23_1830 (UTC) as a reference, the new M1 apparent alignments are:

DOF        Previous value       New value            Apparent change
---------------------------------------------------------------------------
L          -37.1 um             -65.7 um               -28.6 um
T           45.4 um              69.2 um               +23.8 um
V           35.5 um              62.4 um               +27.0 um
R          -62.2 urad           -112.0 urad          -49.7 urad
P           1082.8 urad          1901.1 urad         +818.3 urad
Y           3.9 urad             88.6 urad           +84.8 urad


%%%%%%%%%%%%
Stage: M2
%%%%%%%%%%%%

The suggested (calibrated) M2 OSEMINF gains are
(new UL) = 0.900 * (old UL) = 1.109
(new LL) = 0.838 * (old LL) = 1.082
(new UR) = 0.921 * (old UR) = 1.134
(new LR) = 0.939 * (old LR) = 1.293

The calibration will change the apparent alignment of the suspension as seen by the M2 OSEMs
NOTE: The actual alignment of the suspension will NOT change as a result of the calibration process

The changes are computed as (osem2eul) * gain * pinv(osem2eul).
Using the alignments from 2025-09-23_1830 (UTC) as a reference, the new M2 apparent alignments are:

DOF        Previous value       New value            Apparent change
---------------------------------------------------------------------------
L          -58.3 um             -52.7 um                +5.6 um
P           861.7 urad           772.3 urad          -89.4 urad
Y          -518.0 urad          -520.3 urad           -2.2 urad


%%%%%%%%%%%%
Stage: M3
%%%%%%%%%%%%

The suggested (calibrated) M3 OSEMINF gains are
(new UL) = 0.939 * (old UL) = 1.267
(new LL) = 0.875 * (old LL) = 1.138
(new UR) = 0.903 * (old UR) = 1.170
(new LR) = 0.939 * (old LR) = 1.351

The calibration will change the apparent alignment of the suspension as seen by the M3 OSEMs
NOTE: The actual alignment of the suspension will NOT change as a result of the calibration process

The changes are computed as (osem2eul) * gain * pinv(osem2eul).
Using the alignments from 2025-09-23_1830 (UTC) as a reference, the new M3 apparent alignments are:

DOF        Previous value       New value            Apparent change
---------------------------------------------------------------------------
L          -72.1 um             -65.8 um                +6.4 um
P           923.6 urad           845.0 urad          -78.6 urad
Y          -459.5 urad          -453.6 urad           +5.9 urad

 

We have calculated a GS13 to OSEM calibration of H1 SRM ['M1' 'M2' 'M3'] using HAM5 ST1 drives from 2025-09-23_1830 (UTC).
We fit the response SRM_OSEMINF/HAM5_SUSPOINT to unity between 6 and 15 Hz to get a calibration such that 1 [OSEM m] = [GS13 m]

This message was generated automatically by OSEM_calibration_master.py on 2025-09-27 00:50:36.037056+00:00 UTC

 

%%%%%%%%%%%%%%%%%%%%%%%%%%%%

EXTRA INFORMATION

%%%%%%%%%%%%%%%%%%%%%%%%%%%%


%%%%%%%%%%%%
Stage: M1
%%%%%%%%%%%%
The H1:SUS-SRM_M1_OSEMINF gains at the time of measurement were:
(old) T1: 1.115
(old) T2: 1.178
(old) T3: 1.046
(old) LF: 1.081
(old) RT: 1.142
(old) SD: 1.176

The matrix to convert from the old SRM M1 Euler dofs to the (calibrated) new Euler dofs is:

+1.769    -0.0    +0.0    +0.0    -0.0    -0.014
+0.0    +1.525    -0.0    +0.0    +0.0    +0.0
+0.0    +0.0    +1.77    -0.001    -0.0    +0.0
-0.0    -0.0    -0.224    +1.77    +0.006    -0.0
-0.0    -0.0    -0.761    +0.046    +1.783    -0.0
-2.203    +0.0    -0.0    -0.0    +0.0    +1.769

The matrix is used as (M) * (old EUL dof) = (new EUL dof)
The dof ordering is ('L', 'T', 'V', 'R', 'P', 'Y')

%%%%%%%%%%%%
Stage: M2
%%%%%%%%%%%%
The H1:SUS-SRM_M2_OSEMINF gains at the time of measurement were:
(old) UL: 1.232
(old) LL: 1.291
(old) UR: 1.232
(old) LR: 1.377

To compensate for the M2 OSEM gain changes, any controllers using the M2 OSEMs as inputs must be compensated with gains of:
L gain = 1.113 * (old L gain)
P gain = 1.112 * (old P gain)
Y gain = 1.114 * (old Y gain)

The matrix to convert from the old SRM M2 Euler dofs to the (calibrated) new Euler dofs is:

+0.9    +0.001    +0.001
+0.227    +0.9    -0.02
+0.635    -0.02    +0.9

The matrix is used as (M) * (old EUL dof) = (new EUL dof)
The dof ordering is ('L', 'P', 'Y')

%%%%%%%%%%%%
Stage: M3
%%%%%%%%%%%%
The H1:SUS-SRM_M3_OSEMINF gains at the time of measurement were:
(old) UL: 1.349
(old) LL: 1.300
(old) UR: 1.295
(old) LR: 1.439

To compensate for the M3 OSEM gain changes, any controllers using the M3 OSEMs as inputs must be compensated with gains of:
L gain = 1.094 * (old L gain)
P gain = 1.095 * (old P gain)
Y gain = 1.095 * (old Y gain)

The matrix to convert from the old SRM M3 Euler dofs to the (calibrated) new Euler dofs is:

+0.914    +0.0    +0.0
+0.147    +0.914    -0.025
+0.147    -0.025    +0.914

The matrix is used as (M) * (old EUL dof) = (new EUL dof)
The dof ordering is ('L', 'P', 'Y')

 

Non-image files attached to this report
LHO General
thomas.shaffer@LIGO.ORG - posted 16:38, Friday 26 September 2025 (87165)
Ops Eve Shift Start

TITLE: 09/26 Eve Shift: 2330-0500 UTC (1630-2200 PST), all times posted in UTC
STATE of H1: Observing at 149Mpc
OUTGOING OPERATOR: Ibrahim
CURRENT ENVIRONMENT:
    SEI_ENV state: CALM
    Wind: 11mph Gusts, 6mph 3min avg
    Primary useism: 0.04 μm/s
    Secondary useism: 0.33 μm/s 
QUICK SUMMARY: Locked for 9 hours, calm environment. The ETMY roll mode seems to be under control. It does "breathe" up and down a bit, but it isn't growing.

H1 General
ryan.crouch@LIGO.ORG - posted 16:31, Friday 26 September 2025 (87159)
OPS Monday Day shift summary

TITLE: 09/26 Day Shift: 1430-2330 UTC (0730-1630 PST), all times posted in UTC
STATE of H1: Observing at 150Mpc
INCOMING OPERATOR: TJ
SHIFT SUMMARY: We stayed locked the entire shift, 9 hours at the end of the shift. Secondary microseism is still rising.
LOG:

Start Time System Name Location Lazer_Haz Task Time End
16:48 VAC Pump LVEA N AIP pumping on HAM6 23:43
16:27 TCS Camilla VAP prep lab N Check on parts dimensions, cheeta 16:39
23:20 CAL Dripta Optics lab LOCAL PCAL checks 23:29
H1 SUS (SUS)
ibrahim.abouelfettouh@LIGO.ORG - posted 16:23, Friday 26 September 2025 (87164)
Weekly In-Lock SUS Charge Measurement - FAMIS 28424

Closes FAMIS 28424, last checked in alog 86887.

Measurements did not seem to run last week (and couldn't find an alog for it), but did this week.

ITMX did not run this week - just like the previous check on 09/09.

I didn't capture a screenshot in time but I recall the same message from the last check: 

"Cannot calculate beta/beta2 because some measurements failed or have insufficient coherence!
Cannot calculate alpha/gamma because some measurements failed or have insufficient coherence!
Something went wrong with analysis, skipping ITMX_13_Hz_1440859844"

 

Plots attached.

 

Images attached to this report
H1 SUS (SUS)
ryan.crouch@LIGO.ORG - posted 14:33, Friday 26 September 2025 (87158)
ETMX charge

It seems like the charge on ETMX is increasing as seen by a few different metrics...

Currently the 'ETMX_L3_LOCK_BIAS_OFFSET' we use while locked is +6.05425, the sign is flipped when we are down. Specifically in the PREP_FOR_LOCKING main() fx it's set to -8.9, and it looks to be switching the value as expected.

There's not all that much we can do about this right now, we should keep an eye on it and make sure the values are flipped during maintenance windows (they should be since it's in GRD).

Images attached to this report
H1 SUS
edgard.bonilla@LIGO.ORG - posted 14:24, Friday 26 September 2025 (87162)
Errata for SR3 OSEM calibration [LHO aLog: 85907].

This errata is the SR3 version of [LHO: 87160] that dealt with PR3. 

While double-checking the PR3/SR3 OSEM calibration script, I noticed a typo on the printing output of the function that generated the logpost [LHO: 85907].

No changes need to be made because the calculated M1 OSEM calibrations and M1_DAMP gains are both correct. Plots and other visual documentation is all correct too.

However, the expected alignments posted in [LHO: 85907] were wrong, as the (old EUL) to (new EUL) transformation matrix was accidentally inverted.

 

I post here the corrected script output for the SR3 OSEM calibration for the sake of documentation and transparency. Note that the theoretically calculated alignment values match the observed ones for SR3 too [see attached screenshot]

_____________________________________________________

OSEM calibration of H1:SUS-SR3
Stage: M1
2025-07-22_1530 (UTC).

The suggested (calibrated) M1 OSEMINF gains are
(new T1) = 2.174 * (old T1) = 3.213
(new T2) = 1.610 * (old T2) = 1.517
(new T3) = 1.569 * (old T3) = 1.494
(new LF) = 1.331 * (old LF) = 1.733
(new RT) = 1.374 * (old RT) = 1.494
(new SD) = 1.390 * (old SD) = 1.793

To compensate for the OSEM gain changes, we estimate that the H1:SUS-SR3_M1_DAMP loops must be changed by factors of:
L gain = 0.740 * (old L gain)
T gain = 0.719 * (old T gain)
V gain = 0.545 * (old V gain)
R gain = 0.545 * (old R gain)
P gain = 0.629 * (old P gain)
Y gain = 0.740 * (old Y gain)

The calibration will change the apparent alignment of the suspension as seen by the at the M1 OSEMs
NOTE: The actual alignment of the suspension will NOT change as a result of the calibration process

The changes are computed as (osem2eul) * gain * inv(osem2eul).
Using the alignments from 2025-07-22_1530 (UTC) as a reference, the new apparent alingments are:

DOF        Previous value       New value            Apparent change
---------------------------------------------------------------------------------
L          -5.0 um              -7.7 um                 -2.8 um
T          -21.6 um             -30.0 um                -8.4 um
V           11.8 um              10.6 um                -1.2 um
R          -576.3 urad          -1036.9 urad         -460.6 urad
P          -266.5 urad          -447.4 urad          -180.8 urad
Y          -585.0 urad          -792.6 urad          -207.6 urad

We have estimated a OSEM calibration of H1 SR3 M1 using HAM5 ST1 drives from 2025-05-21_0000 (UTC).
We fit the response M1_DAMP/HAM5_SUSPOINT between 5 and 15 Hz to get a calibration in [OSEM m]/[GS13 m]

This message was generated automatically by OSEM_calibration_SR3.py on 2025-09-26 21:16:58.591270+00:00 UTC

%%%%%%%%%%%%%%%%%%%%%%%%%%%%


EXTRA INFORMATION

The H1:SUS-SR3_M1_OSEMINF gains at the time of measurement were:
(old) T1: 1.478
(old) T2: 0.942
(old) T3: 0.952
(old) LF: 1.302
(old) RT: 1.087
(old) SD: 1.290

The matrix to convert from the old Euler dofs to the (calibrated) new Euler dofs is:

+1.353    +0.0    -0.0    +0.0    -0.0    +0.002
+0.0    +1.39    +0.0    -0.0    -0.0    +0.0
+0.0    +0.0    +1.882    +0.02    -0.0    -0.0
+0.0    -0.0    +4.175    +1.882    +0.007    +0.0
-0.0    -0.0    -0.454    +0.032    +1.59    +0.0
+0.27    -0.0    -0.0    +0.0    +0.0    +1.353

The matrix is used as (M) * (old EUL dof) = (new EUL dof)
The dof ordering is ('L', 'T', 'V', 'R', 'P', 'Y')

 

Images attached to this report
H1 SUS (SUS)
edgard.bonilla@LIGO.ORG - posted 14:00, Friday 26 September 2025 (87160)
Errata for PR3 OSEM calibration [LHO aLog: 86222].

While double-checking the PR3 OSEM calibration script, I noticed a typo on the printing output of the function that generated the logpost [LHO: 86222].

No changes need to be made because the calculated M1 OSEM calibrations and M1_DAMP gains are both correct.

However, the expected alignments posted in [LHO: 86222] were wrong, as the (old EUL) to (new EUL) transformation matrix was accidentally inverted.

 

I post here the corrected script output for the PR3 OSEM calibration for the sake of documentation and transparency. Note that the theoretically expected alignment values are in line with the observed ones [see attached screenshot]

____

OSEM calibration of H1:SUS-PR3
Stage: M1
2025-08-05_1700 (UTC).

The suggested (calibrated) M1 OSEMINF gains are
(new T1) = 1.770 * (old T1) = 2.055
(new T2) = 1.547 * (old T2) = 1.544
(new T3) = 1.443 * (old T3) = 1.511
(new LF) = 1.590 * (old LF) = 1.862
(new RT) = 1.774 * (old RT) = 2.063
(new SD) = 1.543 * (old SD) = 1.639

To compensate for the OSEM gain changes, we estimate that the H1:SUS-PR3_M1_DAMP loops must be changed by factors of:
L gain = 0.596 * (old L gain)
T gain = 0.648 * (old T gain)
V gain = 0.617 * (old V gain)
R gain = 0.617 * (old R gain)
P gain = 0.670 * (old P gain)
Y gain = 0.596 * (old Y gain)

The calibration will change the apparent alignment of the suspension as seen by the at the M1 OSEMs
NOTE: The actual alignment of the suspension will NOT change as a result of the calibration process

The changes are computed as (osem2eul) * gain * inv(osem2eul).
Using the alignments from 2025-08-05_1700 (UTC) as a reference, the new apparent alingments are:

DOF        Previous value       New value            Apparent change
---------------------------------------------------------------------------------
L          -57.1 um             -97.3 um               -40.2 um
T          -101.3 um            -156.3 um              -55.0 um
V           62.4 um              106.7 um              +44.4 um
R           433.5 urad           819.6 urad          +386.1 urad
P          -631.8 urad          -981.5 urad          -349.7 urad
Y          -166.7 urad          -345.9 urad          -179.3 urad

We have estimated a OSEM calibration of H1 PR3 M1 using HAM2 ST1 drives from 2025-05-21_0000 (UTC).
We fit the response M1_DAMP/HAM2_SUSPOINT between 5 and 15 Hz to get a calibration in [OSEM m]/[GS13 m]

This message was generated automatically by OSEM_calibration_SR3.py on 2025-09-26 20:41:09.411215+00:00 UTC

%%%%%%%%%%%%%%%%%%%%%%%%%%%%


EXTRA INFORMATION

The H1:SUS-PR3_M1_OSEMINF gains at the time of measurement were:
(old) T1: 1.161
(old) T2: 0.998
(old) T3: 1.047
(old) LF: 1.171
(old) RT: 1.163
(old) SD: 1.062

The matrix to convert from the old Euler dofs to the (calibrated) new Euler dofs is:

+1.682    +0.0    -0.0    +0.0    -0.0    +0.007
+0.0    +1.543    +0.0    -0.0    -0.0    +0.0
+0.0    +0.0    +1.633    +0.01    -0.001    -0.0
+0.0    -0.0    +1.964    +1.633    +0.017    +0.0
-0.0    -0.0    -1.154    +0.081    +1.495    +0.0
+1.148    -0.0    -0.0    +0.0    +0.0    +1.682

The matrix is used as (M) * (old EUL dof) = (new EUL dof)
The dof ordering is ('L', 'T', 'V', 'R', 'P', 'Y')

 

Images attached to this report
H1 General
ryan.crouch@LIGO.ORG - posted 12:09, Friday 26 September 2025 (87157)
OPS Friday DAY midshift update

STATE of H1: Observing at 152Mpc

Images attached to this report
LHO VE
david.barker@LIGO.ORG - posted 10:16, Friday 26 September 2025 (87156)
Fri CP1 Fill

Fri Sep 26 10:09:31 2025 INFO: Fill completed in 9min 27secs

Gerardo confirmed a good fill curbside.

Images attached to this report
H1 PSL
ryan.crouch@LIGO.ORG - posted 08:05, Friday 26 September 2025 (87110)
PSL Status Report Weekly FAMIS 26663

Closes FAMIS26663, last checked in alog87026


Laser Status:
    NPRO output power is 1.858W
    AMP1 output power is 70.03W
    AMP2 output power is 139.0W
    NPRO watchdog is GREEN
    AMP1 watchdog is GREEN
    AMP2 watchdog is GREEN
    PDWD watchdog is GREEN

PMC:
    It has been locked 2 days, 20 hr 56 minutes
    Reflected power = 24.91W
    Transmitted power = 104.2W
    PowerSum = 129.2W

FSS:
    It has been locked for 0 days 2 hr and 13 min
    TPD[V] = 0.5372V

ISS:
    The diffracted power is around 4.2%
    Last saturation event was 0 days 2 hours and 13 minutes ago


Possible Issues:
    PMC reflected power is high

H1 General
ryan.crouch@LIGO.ORG - posted 07:32, Friday 26 September 2025 (87154)
OPS Friday Day shift start

TITLE: 09/26 Day Shift: 1430-2330 UTC (0730-1630 PST), all times posted in UTC
STATE of H1: Observing at 148Mpc
OUTGOING OPERATOR: Ibrahim
CURRENT ENVIRONMENT:
    SEI_ENV state: CALM
    Wind: 9mph Gusts, 6mph 3min avg
    Primary useism: 0.02 μm/s
    Secondary useism: 0.21 μm/s 
QUICK SUMMARY:

LHO General
ibrahim.abouelfettouh@LIGO.ORG - posted 04:06, Friday 26 September 2025 (87153)
OPS OWL Shift: Round 2

Got notified again and since I hadn't slept yet, was still logged in with some ideas of what was causing issues.

H1 got stuck at input align and a quick looksy through the alog found this parcel of frustration from TJ's alog 86095. Using the wiki and following this, I found that indeed:

IM's did not quite restore to an aligned state post EQ so I trended back OSEMs and moved sliders:

This worked! 

But as then I couldn't lock SRY, so I moved SRM a bit in order to maximize AS_A centering peaks!

This also worked!

Back to LOCKING

LHO General (Lockloss, SEI)
ibrahim.abouelfettouh@LIGO.ORG - posted 00:35, Friday 26 September 2025 (87152)
OPS OWL Shift: 5.9 Oregon Earthquake Lockloss 06:47 UTC

A 5.9 EQ from Oregon hit H1 quite violently and tripped:

HAM1 ISI, HAM2 ISI, HAM2

IM1 (M1), IM2 (M1), IM3 (M1), IM4 (M1)

MC1 (M1), MC2 (M1), MC3 (M1)

PRM (M1,2,3), PR2 (M1), SRM (M1,2,3), SR2 (M1), SR3 (M1)

FC1 (M1,2,3), FC2 (M1,3)

Along with their respective ISIs (ST1) and the QUAD ISIs (though I untripped a bit too quickly to note the exact ISIs I untripped so will append this tomorrow when I can trend without lag).

A few guardians also stalled so I unstalled them. I attached an overview of verbal trips and overview screen.

IFO is back to LOCKING and EQ is mostly passed. I've reset myself as the OWL.

Images attached to this report
H1 General
oli.patane@LIGO.ORG - posted 22:00, Thursday 25 September 2025 (87151)
Ops EVE shift end

TITLE: 09/26 Eve Shift: 2330-0500 UTC (1630-2200 PST), all times posted in UTC
STATE of H1: Wind
INCOMING OPERATOR: Ibrahim
SHIFT SUMMARY: Currently relocking and in LASER_NOISE_SUPPRESSION. One lockloss today due to the wind, and relocking has been taking a while because of the wind. We were worried about the ETMY Roll mode earlier, but it ended up coming back down on its own. Maybe we should keep an eye on it over the weekend, but it seemed like the current setting are doing okay. The ion pump is still running in the LVEA - since the lockloss was so late in the evening, there were no vacuum people on site to turn it off, but that's okay. 
LOG:

23:30 UTC Observing and Locked for over 11 hours
    00:22 GRB-Short E603710
02:27 Lockloss
    - ALSY needed help
    - Constant ALS locklosses because of high wind, so sitting in DOWN for a while

Start Time System Name Location Lazer_Haz Task Time End
16:48 VAC Pump LVEA N AIP pumping on HAM6 23:43
02:26 PCAL Tony PCAL Lab y(local) Setting up measurement 02:41
H1 General (Lockloss)
oli.patane@LIGO.ORG - posted 19:39, Thursday 25 September 2025 (87150)
Lockloss

Lockloss at 2025-09-26 02:37 UTC after 14.5 locked due to high wind :( We were riding it out really well up until now 

Images attached to this report
H1 ISC
elenna.capote@LIGO.ORG - posted 17:29, Thursday 25 September 2025 - last comment - 11:11, Monday 29 September 2025(87149)
HARD loop update: open loop gain measurements, loop adjustments

Here is a summary of some results from the open loop gain measurements of DHARD Y and CHARD Y, and the implementation of a new CHARD P low pass:

DHARD Y

I measured the DHARD Y open loop gain, results shown here. The dark blue trace shows the original measurement, showing 17 degrees of phase margin and gain peaking of 10 dB. Looking at the loop design, there are three different boost filters applied to DHARD Y, compared here. These boosts in combination seem to be destroying all the phase of the loop. I took a measurement with the 0.9 Hz boost disengaged (FM3), which is shown in the green trace. Then, I disengaged the 0.5 Hz boost (FM4) and remeasured, shown in the red trace. This improved the phase margin to 32 degrees. This obviously resulted in less microseismic suppression. I adjusted the 0.5 Hz boost (FM4) and decided we should operate without the boost in FM3. This plot compares the original loop error signal and RMS with all three boosts (gold), the error signal and RMS without FM3 and FM4 boosts (green) and then error signal and RMS with the updated FM4 boost (red). The RMS increased 50% without both boosts on, the improved boost returns the RMS to that value. There is now more phase margin in the loop. Updated in guardian and ASC high gain script, SDFed (1,2).

CHARD Y

I measured the CHARD Y open loop gain, results shown here. The file had an old reference trace from 2023, shown in bluegreen in the reference. The gray trace shows the first measurement I made today of CHARD Y. The gain appeared to be way too low. I raised the gain to match the old reference, which was a gain increase of 6 dB. Here is a comparison of the RMS of CHARD Y from 14 hours ago (bluegreen reference) and now (red live). The microseism level is the same between these two measurements. Overall, this reduces the RMS of the loop, so I think this is a good adjustment. This is updated in the guardian and ASC high gain script, also SDFed.

CHARD P

I implemented a new CHARD P low pass filter to reduce CHARD P coupling that is apparent in coherence measurements (example).

Here is a comparison of the old controller (red) with the new controller (blue). This replaces the lowpass filter in FM8 with the filter in FM9. I also disengaged the old 200 Hz lowpass that was previously in FM10, as it wasn't doing much. SDFs (1,2). Guardian code and ASC high gain script updated.

The coherence of DARM with CHARD P has reduced, as expected, and increased for CHARD Y, also as expected. I have since created a new lowpass for CHARD Y that should reduce the coherence and is ready for testing at the next opportunity (comparison).

Images attached to this report
Comments related to this report
elenna.capote@LIGO.ORG - 11:11, Monday 29 September 2025 (87199)

Here is an improved CHARD Y lowpass at 10 Hz. Saved in FM6. The sacrifice is about 7 degrees, my previous measurement showed that there is 37 degrees at the UGF.

I don't see a difference in DARM, but the DARM coherence with CHARD Y has dropped. There is no change in the loop RMS either (comparing two times with similar microseism levels).

I updated the guardian to use this filter, and I also edited the ASC higain script.

SDFed.

Images attached to this comment
LHO General
ryan.short@LIGO.ORG - posted 16:31, Thursday 25 September 2025 (87148)
Ops Day Shift Summary

TITLE: 09/25 Day Shift: 1430-2330 UTC (0730-1630 PST), all times posted in UTC
STATE of H1: Observing at 147Mpc
INCOMING OPERATOR: Oli
SHIFT SUMMARY: H1 has been locked the whole day so far; current lock stretch is up to almost 11.5 hours. The ETMY roll mode is slightly more rung up than it has been in the past few days, but maybe not egregiously so; Oli will keep an eye on it this evening. Other than commissioning time this morning, it's been a quiet shift.

LOG:

Start Time System Name Location Lazer_Haz Task Time End
16:48 VAC Pump LVEA N AIP pumping on HAM6 Ongoing
17:52 SEI Jim, Mitchell MX N Looking at 3IFO HEPI parts 18:36
21:29 FIT Matt Y-arm N On a run 22:12
H1 SEI (SEI, SUS)
jeffrey.kissel@LIGO.ORG - posted 10:17, Tuesday 23 September 2025 - last comment - 18:56, Friday 26 September 2025(87093)
H1 ISI HAM2 and ISI HAM5 EUL2CART Suspension Point Drive Matrices Changed from PR3/SR3 to PRM/SRM
J. Kissel

In prep for measuring the absolute calibration PRM and SRM OSEMs, I've changed the ISI HAM2 / HAM5 suspension point drive matrices to project from the PRM and SRM suspension points rather than PR3 and SR3 what we used when calibrating those top mass OSEMs.

Here's the method for installing these matrices:

>> addpath /ligo/svncommon/SeiSVN/seismic/Common/MatlabTools/
>> load /opt/rtcds/userapps/trunk/isc/common/projections/ISI2SUS_projection_file.mat;
>> ham2 = ISI2SUSprojections.h1.prm.EUL2CART;
>> fill_matrix_values('H1:ISI-HAM2_SUSPOINT_EUL2CART',ham2)
>> ham5 = ISI2SUSprojections.h1.srm.EUL2CART;
>> fill_matrix_values('H1:ISI-HAM5_SUSPOINT_EUL2CART',ham5)

Attached are screenshots of the matrix MEDM screens themselves and the SDF accept in the OBSERVE .snap files. 
Since these are used and moved around to calibrate each of the SUS in the chamber, and it's so simple to restore if lost, I'm not bothering to save the values in the ISI's safe.snap.
Images attached to this report
Comments related to this report
brian.lantz@LIGO.ORG - 09:26, Friday 26 September 2025 (87155)

WARNING:  We need to check this before we use it again. These projections were done for the sensors, not the actuators. 

The EUL basis -> ISI drives actuator matrix needs to be calculated and added to the suspoint projections script and data in the repo. Edgard says this should be the transpose of the sensor matrix, not the inverse. Documentation is in progress.
(EUL2CART and CART2EUL are both for the sensor projection, and are inverses of each other)

edgard.bonilla@LIGO.ORG - 18:56, Friday 26 September 2025 (87167)

Ohp. I made a mistake here.

The drive matrix calculation bit is true about applied drives. However, because the ISI drive requests here are made at the error point of the ISO loops, the inverse is actually correct. Nevermind what I said before.

Apologies for the confusion.

H1 SUS (SEI, SUS)
edgard.bonilla@LIGO.ORG - posted 11:01, Wednesday 06 August 2025 - last comment - 14:11, Friday 26 September 2025(86222)
OSEM calibration of H1:SUS-PR3

Oli, Ivey, Edgard.

We used Oli's measurements from [LHO: 86204] to do an OSEM calibration for the PR3 M1 OSEMs. Here are the outputs of the calibration script.
_______________________________________

OSEM calibration of H1:SUS-PR3
Stage: M1
2025-08-05_1700 (UTC).

The suggested (calibrated) M1 OSEMINF gains are
(new T1) = 1.770 * (old T1) = 2.055
(new T2) = 1.547 * (old T2) = 1.544
(new T3) = 1.443 * (old T3) = 1.511
(new LF) = 1.590 * (old LF) = 1.862
(new RT) = 1.774 * (old RT) = 2.063
(new SD) = 1.543 * (old SD) = 1.639

To compensate for the OSEM gain changes, we estimate that the H1:SUS-PR3_M1_DAMP loops must be changed by factors of:
L gain = 0.596 * (old L gain)
T gain = 0.648 * (old T gain)
V gain = 0.617 * (old V gain)
R gain = 0.617 * (old R gain)
P gain = 0.670 * (old P gain)
Y gain = 0.596 * (old Y gain)

The calibration will change the apparent alignment of the suspension as seen by the at the M1 OSEMs
NOTE: The actual alignment of the suspension will NOT change as a result of the calibration process

The changes are computed as (osem2eul) * gain * inv(osem2eul).
Using the alignments from 2025-08-05_1700 (UTC) as a reference, the new apparent alingments are:

DOF        Previous value       New value            Apparent change
---------------------------------------------------------------------------------
L          -57.1 um             -33.6 um               +23.5 um
T          -101.3 um            -65.6 um               +35.7 um
V           62.4 um              36.6 um               -25.8 um
R           433.5 urad           225.7 urad          -207.8 urad
P          -631.8 urad          -406.5 urad          +225.2 urad
Y          -166.7 urad          -76.1 urad           +90.5 urad

We have estimated a OSEM calibration of H1 PR3 M1 using HAM2 ST1 drives from 2025-05-21_0000 (UTC).
We fit the response M1_DAMP/HAM2_SUSPOINT between 5 and 15 Hz to get a calibration in [OSEM m]/[GS13 m]

This message was generated automatically by OSEM_calibration_SR3.py on 2025-08-06 01:07:57.985744+00:00 UTC

%%%%%%%%%%%%%%%%%%%%%%%%%%%%


EXTRA INFORMATION

The H1:SUS-PR3_M1_OSEMINF gains at the time of measurement were:
(old) T1: 1.161
(old) T2: 0.998
(old) T3: 1.047
(old) LF: 1.171
(old) RT: 1.163
(old) SD: 1.062

The matrix to convert from the old Euler dofs to the (calibrated) new Euler dofs is:

+0.596    -0.0    +0.0    -0.0    +0.0    -0.003
+0.0    +0.648    -0.0    +0.0    +0.0    -0.0
-0.0    +0.0    +0.617    -0.004    +0.001    +0.0
+0.0    +0.0    -0.748    +0.617    -0.007    -0.0
+0.0    +0.0    +0.517    -0.036    +0.67    -0.0
-0.407    +0.0    -0.0    +0.0    -0.0    +0.596

The matrix is used as (M) * (old EUL dof) = (new EUL dof)
The dof ordering is ('L', 'T', 'V', 'R', 'P', 'Y')

Images attached to this report
Comments related to this report
edgard.bonilla@LIGO.ORG - 14:11, Friday 26 September 2025 (87161)SUS

The calibration values posted here are correct, but the theoretical alignment values are incorrect. See the corrected post from Sep 26th, 2025.

[CORRECTED LOGPOST LHO: 87160]

H1 SUS (SEI, SUS)
ivey.zhong@LIGO.ORG - posted 09:32, Tuesday 22 July 2025 - last comment - 14:32, Friday 26 September 2025(85907)
OSEM calibration of H1:SUS-SR3
OSEM calibration of H1:SUS-SR3
Stage: M1
2025-07-22_1530 (UTC).

The suggested (calibrated) M1 OSEMINF gains are
(new T1) = 2.174 * (old T1) = 3.213 
(new T2) = 1.610 * (old T2) = 1.517 
(new T3) = 1.569 * (old T3) = 1.494 
(new LF) = 1.331 * (old LF) = 1.733 
(new RT) = 1.374 * (old RT) = 1.494 
(new SD) = 1.390 * (old SD) = 1.793 

To compensate for the OSEM gain changes, we estimate that the H1:SUS-SR3_M1_DAMP loops must be changed by factors of: 
L gain = 0.740 * (old L gain)
T gain = 0.719 * (old T gain)
V gain = 0.545 * (old V gain)
R gain = 0.545 * (old R gain)
P gain = 0.629 * (old P gain)
Y gain = 0.740 * (old Y gain)

The calibration will change the apparent alignment of the suspension as seen by the at the M1 OSEMs
NOTE: The actual alignment of the suspension will NOT change as a result of the calibration process

The changes are computed as (osem2eul) * gain * inv(osem2eul).
Using the alignments from 2025-07-22_1530 (UTC) as a reference, the new apparent alingments are:

DOF        Previous value       New value            Apparent change
---------------------------------------------------------------------------------
L          -5.0 um              -3.1 um                 +1.8 um
T          -21.6 um             -15.5 um                +6.1 um
V           11.8 um              9.8 um                 -2.0 um
R          -576.3 urad          -327.5 urad          +248.9 urad
P          -266.5 urad          -158.3 urad          +108.2 urad
Y          -585.0 urad          -431.9 urad          +153.1 urad

We have estimated a OSEM calibration of H1 SR3 M1 using HAM5 ST1 drives from 2025-05-21_0000 (UTC).
We fit the response M1_DAMP/HAM5_SUSPOINT between 5 and 15 Hz to get a calibration in [OSEM m]/[GS13 m]

This message was generated automatically by OSEM_calibration_SR3.py on 2025-07-22 16:24:05.000267+00:00 UTC

%%%%%%%%%%%%%%%%%%%%%%%%%%%% 


EXTRA INFORMATION 

The H1:SUS-SR3_M1_OSEMINF gains at the time of measurement were:
(old) T1: 1.478 
(old) T2: 0.942 
(old) T3: 0.952 
(old) LF: 1.302 
(old) RT: 1.087 
(old) SD: 1.290 

The matrix to convert from the old Euler dofs to the (calibrated) new Euler dofs is:

+0.74	-0.0	+0.0	-0.0	+0.0	-0.001
+0.0	+0.719	-0.0	+0.0	+0.0	-0.0
-0.0	+0.0	+0.545	-0.006	+0.0	+0.0
+0.0	+0.0	-1.209	+0.545	-0.003	-0.0
+0.0	+0.0	+0.18	-0.013	+0.629	-0.0
-0.148	+0.0	-0.0	+0.0	-0.0	+0.74

The matrix is used as (M) * (old EUL dof) = (new EUL dof)
The dof ordering is ('L', 'T', 'V', 'R', 'P', 'Y')

Please see the attached images of before calibrating and after calibrating.
Images attached to this report
Comments related to this report
oli.patane@LIGO.ORG - 12:31, Tuesday 22 July 2025 (85916)

Comparing these new OSEMINF gains to the gains we got last time we did this (84367) (before the satamp swap), they are pretty similar:

OSEM Previous Calculated OSEMINF gains (84367) New Calculated OSEMINF gains (85907) Percent difference (%)
T1 3.627 3.213 12.1
T2 1.396 1.517 8.3
T3 1.345 1.494 10.4
LF 1.719 1.733 0.8
RT 1.490 1.494 0.2
SD 1.781 1.793 0.6

So that's another indicator that the sat amp swap did not have much of an effect on the suspension response to suspoint excitations

edgard.bonilla@LIGO.ORG - 14:32, Friday 26 September 2025 (87163)SUS

The calibration values posted here are correct, but the theoretical alignment values are incorrect. See the corrected post from Sep 26th, 2025.

[CORRECTED LOGPOST LHO: 87162]

Displaying reports 4521-4540 of 89207.Go to page Start 223 224 225 226 227 228 229 230 231 End