CDS status as of 12:34

Here is what we know is not running (in no particular order)

h1cdsrfm (end station adnaco boxes not responding)

ncalex

brs_ex, brs_ey

hws_ex, hws_ey

mains_ex

chiller_ex, chiller_cs

MSR timing master 9th port has no link, missing DTS fanout?

 

Comments related to this report
david.barker@LIGO.ORG - 12:44, Saturday 30 May 2026 (90392)

We spoke with Patrick and he says all the Beckhoff items in the list can wait till Monday. Ditto HWS.

Erik is working on the h1cdsrfm end-station Adnaco and Timing Master issues. He is on his way to the end stations and H2 building.

david.barker@LIGO.ORG - 14:02, Saturday 30 May 2026 (90394)

Erik went to the DTS, EX and EY:

 . Both end station cdsrfm chassis have been turned on.

 . Both end station HWS are operational.

 . The EY GPS receiver went red for a while, then got position lock and went green. No action was needed.

 . DTS timing fanout was powered up. The timing system is now green again.

EDC is now down to 229 disconnected channels, these are:

NCALX, BRS_EX, BRS_EY, MAINS_EX, CHILLER_EX, CHILLER_EY

These will remain off until Monday.

Also the EY WAP is offline, will be fixed on Monday.

Erik is now recovering some FOM wall monitors.

 

 

 

LHO VE (VE)
jordan.vanosky@LIGO.ORG - posted 12:31, Saturday 30 May 2026 - last comment - 16:48, Saturday 30 May 2026(90389)
VAC Recovery After Site Power Issue

Following the power issue I came out to the site to check on the purge air, pump carts, RGAs, etc.

The Kobelco had an audible alarm, but was still running. Since the interface screen is dead I could not see what the exact alarm was. Drying towers were also not running, though the dewpoint monitor was still reading -75C. I isolated the purge air at the ball valve past the drying towers, then reset both the compressor and the drying towers. I let the system run isolated for ~30 minutes to make sure dewpoint was stable, then opened the line back to the LVEA.

The CP1 turbo was still running, but the solenoid valves on the foreline had closed. I closed the gate valve to the CP volume, and closed the manual o-ring valve on the turbo foreline. Then reset the cart to open the solenoid valves. Once foreline pressure was stable I then opened the foreline o-ring valve and finally opened the CP gate valve. The pressure internal to the cryopump quickly stabilized, and the pressure never got above 1E-7 Torr since the turbo was still spinning. See attached striptool plot (Thanks Gerardo).

Next up was the XBM turbostation which had tripped completely, the turbo/forepumps/and solenoid valves all tripped, so again I closed the gate valve to the XBM and restarted the turbo station. Once the turbo was back to full speed and pressures on either side of the gate valve looked ok, I opened the gate valve.

The three aux carts in use (GV5 annulus/corner rga/HAM6 rga) all had the pumps still running but the solenoid valve had tripped and closed. Pressures were all still ok (<1e-4 Torr) so I reopened the solenoid valves, waited for pressure to drop and stabilize, then set the carts back on the interlocks. RGA trees were isolated from aux carts and were pumped by small ion pump, so no potential backstreaming into RGA volumes.

Finally, I went to the VPW to check on the vacuum ovens. VBOB had no issues, the turbopumps, forepump, and heaters were all running normally. VBOD is vented and was not baking, though the RGA scroll pump had tripped off, turbo was still running. I closed the foreline valve, and restarted the scroll pump and then opened the foreline valve once the foreline pressure was ok. VBOC had a couple issues, the RGA scroll and turbo both tripped off, so I isolated the turbo and restarted the scroll pump first then spun up the turbo and opened back to the RGA tree. The oven heaters had also tripped off. The oven was baking at 150C and the temp had dropped to 130C by the time I arrived, so I reset the heaters and made sure temperature was ramping back up to 150C.

I also verified all of the chamber cleanrooms were still running ok (HAM1/2, HAM3, biergarten, BBSS test stand cleanroom, BSC2 fan bank, and HAM6 cleanroom).

Leaving site now.

Images attached to this report
Comments related to this report
jordan.vanosky@LIGO.ORG - 16:48, Saturday 30 May 2026 (90399)VE

Well, it's Groundhog Day...again.

Came out to the site after the 2nd power glitch. The same pumps had the same issues found for the morning power glitch. I have reset the Kobelco, CP1 pump cart, aux carts, XBM turbopump, and the VPW vacuum ovens. Same procedure as above. Attached is a picture of the CP1 pump cart status and the XBM turbostation as found after the power glitch.

 

Images attached to this comment
H1 CDS
david.barker@LIGO.ORG - posted 10:46, Saturday 30 May 2026 - last comment - 12:34, Saturday 30 May 2026(90386)
Site Power Issue 09:50, all front ends down.

We are investigating a power issue on site which took down all the front ends. We are starting the recovery process.

Initially we thought it was contained to the MSR, but the DTS, Mech Room and end stations are showing problems and reboots.

Erik is on his way to the site. Jordan is on site looking at the vacuum system.

Comments related to this report
david.barker@LIGO.ORG - 12:07, Saturday 30 May 2026 (90388)

FMCS has been mainly restored.

All the frontends have been power cycled, they all came back except h1sush12.

EDC required a power cycled of h1susauxb13 to get going.

h1sush12 has losts its 3rd Adnaco backplane in its IO Chassis (has the 4th ADC on it). Erik is in the CER replacing this.

Jordan reports this was a strange outage, with a seemingly random scattering of pumps impacted across the site.

We same something similar, most but not all FOMs down, but most workstations rode through.

david.barker@LIGO.ORG - 12:34, Saturday 30 May 2026 (90390)

Erik's swap of the 3rd Adnaco backplane on h1sush12 fixed the issue, we can now see the 4th ADC and the models are running. 

I have untripped all the SWWDs with the exception of BSC2.

DAQ is good.

H1 CDS
david.barker@LIGO.ORG - posted 09:07, Saturday 30 May 2026 - last comment - 10:46, Saturday 30 May 2026(90385)
Start of TW0 offload of last 6 months of raw minute trend files to permanent storage

WP13772 TWO Offload

Dave

This morning I started the copy of TW0's raw minute files which have accumulated since 09dec2025 from local SSD-RAID to archive spinning media (h1ldasgw0).

As was done for the last offload in December 2025, following the DC0/FW0 consolidation done 18nov2025 by Jonathan, I am again using h1daqtw0 itself to do the copy. Normally the offload is done by the framewriter, which is still the case on the 1-leg.

The old files were frozen at GPS 1464188058 (07:54:00 Sat 30 May 2026 PDT) prior to offload.

NDS0 was restarted at 08:03 with a temporary configuration to serve the past 6 months of data from its temporary location on TW0 while the copy proceeds.

The copy was started on TW0 at 08:54. It usually takes just over a day to complete.

Comments related to this report
david.barker@LIGO.ORG - 10:46, Saturday 30 May 2026 (90387)

I've stopped this due to the power issue.

LHO General
ryan.short@LIGO.ORG - posted 16:34, Friday 29 May 2026 (90383)
Ops Day Shift Summary

TITLE: 05/29 Day Shift: 1430-2330 UTC (0730-1630 PST), all times posted in UTC
STATE of H1: Planned Engineering
INCOMING OPERATOR: None
SHIFT SUMMARY: Today, HAM7 was vented and most bolts removed from doors while beam alignment continued in HAMs 2 and 3. The LVEA remains Laser HAZARD.
LOG:

Start Time System Name Location Lazer_Haz Task Time End
19:29 SAF Laser HAZARD LVEA YES LVEA is Laser HAZARD Ongoing
14:41 FAC Randy LVEA - Craning table to W-bay 14:59
15:24 VAC Jordan LVEA - Venting HAM7 17:59
15:36 FAC Kim LVEA - Technical cleaning 18:12
15:40 SAF Richard O. Arms - Inspecting beam tube enclosure 18:44
15:40 VAC Randy LVEA - Venting HAM7 17:13
16:43 ISC Keita LVEA Y HAM2 alignment 19:25
17:11 ISC Jennie LVEA Y HAM2 alignment 19:24
17:48 SPI Jeff Opt Lab Local SPI work 18:13
18:47 SEI Shoshana H2 PSL - CRS builds 19:39
19:35 VAC Jordan, Randy LVEA - Breaking bolts on HAM7 20:30
20:24 ISC Keita, Jennie LVEA Y HAM2/3 alignment 23:32
22:30 EPO Disha +2 LVEA - Tour 23:11
22:50 VAC Jordan LVEA - Checking RGA bakeout 22:56
H1 SPI (ISC, SEI, SPI, SQZ)
jeffrey.kissel@LIGO.ORG - posted 16:22, Friday 29 May 2026 - last comment - 08:52, Friday 05 June 2026(90382)
2026-05-26 thru 2026-05-29 SPI Pathfinder Update
J. Kissel, S. Koehlenbeck [remote], J. Wright, M. Simmonds 

Here, we post an aLOG to cover the whole week's slog, picking up where we we left off at that end of last week (LHO:90332). 

%%%%%%%%%%%%%
Executive Summary: the remaining outstanding issue to solve before instal for the SPI pathfinder is the irregular and intermittent drift in heterodyne efficiency in the SPI's MEAS IFO (item (3) from the list of issues after finishing re-assembly up to D2400107-v5 after ECR E2600106). Importantly, we've seen this issue in the MEAS IFO even with the previous version of the assembly back in Mar 2026.

After a week of hard work, we've ruled out just about everything that it could be *except* for flaws in the alignment system of the picomotor-actuated IXM100 mirror mounts which steer the MEAS beam to the MEAS IFO (see D2400107 for the annotated layout).
%%%%%%%%%%%%%

I spend the rest of the aLOG summarizing what we've ruled out and how. Remember -- thru out all of these studies, the REF IFO remains a rock-solid high efficiency, and the power monitor PDs so the input power on the MEAS and REF is quite stable.
And a reminder for those not-so-versed in heterodyne interferometers, the primary metric is the efficiency, defined as 
    eta = [peak-to-peak beat note amplitude] / (2 * beat note mean)
(nominally 100% if the mode overlap between two interfered beams is perfect).
"Drift" of this efficiency means that -- without 

Electronics Issues with the IFO MEAS PDs.
    - Suspected cause: "maybe the bias voltage is drifting?" "Something's going on with the electronic ground because we're only looking at the positive leg?"
    - RULED OUT: we swapped the REF B PD (which had been measuring a rock-solid, high efficiency from the REF IFO) into the MEAS B PD position, and had it measure the MEAS IFO beam. The drift was measured by the REF B PD as well. This convinces us that "it's on the incoming interfered beam.
    - PLUS: The bias voltage is supplied by a single circuit for all PDs in the ISIK transceiver system, so the bias-related issues would be common to REF or MEAS PDs.

Spurious drive on the the picomotors
    - Suspected cause: "maybe the ambient electric field in the room is driving the floating pins of the picomotors, pushing the mirrors around?"
    - RULED OUT: At the start of the week, the picomotor signal chain was hooked up as designed from motor might-mouse to quadrupus to mock feedthru and out a ~6 ft D25 in-air cable that had been used for testing. 
       (a) Just like we'd already done with the PDs, we hooked up ever single picomotor pin to rack power supply ground via a breakout board and clip leads at the end of the in-air cable. Still see drifts. 
       (b) We also tried simply disconnecting all picomotors at their might-mouse connector. Still see drifts.

Clipping along the MEAS path into the MEAS IFO
    - Suspected cause: "If there's some sort of clipping anywhere, you lose efficiency. If it's just barely clipping, the clipper might be moving / breathing with the environment."
    - RULED OUT: 
       (a)Checked centering on M_M1, M_B4, M_M2, M_B3, and the two MEAS IFO PDs, and can confirm they're either
           :: On Optics -- offset in yaw by design (but still several beam diameters away from the optic barrel in REFL or TRANS), or 
           :: Well-centered.
       (b) We'd started the week with the M_M4 and M_M5 mirror mounts and adapters in place (with no dump in either). The beam comfortably goes through the transmission ports of both adapters. But, over the course of the week, as we ruled out "everything else" out, we removed them so now they're off the board. We still see drift.
       (c) Confirmed that "tight-squeezes" between beam dumps still allow for at least ~1x beam diameter of clearance (on an IR card).

Optics' Quality, dust and schmutz
    - Suspected cause: "If there's a scratch or schmutz on the optic, then maybe as the beam alignment drifts, the optical quality of the reflected beam is intermittently spoiled."
    - RULED OUT: We replaced all optics in the MEAS path with just-as-good, same production/coating run, equally class-A cleaned, high quality mirrors. Still see drifts.

Beam quality and Optical Mode-shape
    - Suspected cause: "We haven't found anything, so let's look at the beam shape on a profiler. This should be the definitive answer."
    - RULED OUT: We removed IFO_MEAS_B, and projected the beam on to a WinCam beam profiler head, and read it's data out in the WinCam software. We looked at the beam both with a very slow heterodyne beat-note of 250 mHz, and the nominal 4096 Hz (adjusting the modulation frequency at our commercial RF source's digital interface).
        (a) With the MEAS IFO's alignment just tuned up, Compared mode shape and alignment during episodes of high and low efficiency, and we see nothing but excellent beam shape. (In the slow-beat-note-configuration) the only difference in profile results is the expected lower intensity when the efficiency was low.
        (b) We deliberately misaligned the REF and MEAS beams going into the MEAS IFO such that both beams still visible on the WinCam profile, but not interfering. No movement of beams, no mode shape change, no beam diameter change, nothing that would cause the efficiency drift.

Polarization
    - Suspected cause: "The last thing that it could be if it's not mode shape / quality / alignment is polarization drift..."
    - RULED OUT: With the same IFO_MEAS_B beam, we inserted a polarizing beam splitter and monitored the s-pol power in the reflected port.  S-pol (max) power (at peaks of beat note) is stable at ~10-15 [microWatt] during periods high and low efficiency. The designed p-pol light at IFO is at the 5-10 [milliWatt] level, so the extinction ratio is awesome. And we still see drifts. This also rules out, e.g. the nightmare scenario that the optics' mount PEEK set screw -- only on the MEAS path optics -- are cranked on the optic so hard that is causes birefringence.

    - PLUS: if there was a board-level polarization drift, the REF IFO would also be seeing this same drift.
 
Optical Power fluctuations (Sanity Check)
    - Suspected cause: "I know you don't see any drift in the REF IFO, but ... is the input power drifting?"
    - RULED OUT: 
        (a) The REF IFO beam samples the same beams as the MEAS IFO, and
        (b) Yes, we've had the power monitor PDs up on the o-cope for days, and we see no obvious or reproducible correlation.

RF Modulation Modulation power fluctuations (Sanity Check)
    - Suspected cause: "I know you don't see any drift in the REF IFO, but ... did you check the RF electronics?" 
    - RULED OUT: Yup, we've had the RF power monitor outputs of the laser prep chassis on the scope most of the time, and these are rock-solid and at the expected level.

Environment (Insanity Check)
    - Suspected Cause: "The only thing that intermittently drifts on the minutes time-scales you're seeing is things like air currents and thermal effects."
    - RULED OUT: We tried SO MANY different combinations of 
        (a) Clean room Lights ON/OFF
        (b) Room Lights ON/OFF
        (c) Clean room Fans ON/OFF
        (d) People in/out of clean room
        (e) People in different positions in the clean room
      and none of these showed obvious or reproducible correlation.

Conclusion -- It's gotta be the mechanical assembly of the picomotors in the IXM100 mounts.
The picomotor-actuated assembly process was documented in LHO:87497 following the assembly procedure E2500163.
 
[1] The most accurate mechanical drawing we have the IXM mount itself D1100362
[2] The vendor drawings of the picomotor E1000197
[3] The most accurate assembly of a pico-actuated IXM mounts D1500494 and D2100433
[4] The SPI's drawings for its IXM mounts D2400144 and D2400145

Looking at the assemblies:
    - We're worried that the pico-motor "stopper nut" is pushing the movable-mounting plate (item 1 in [1]), rather than the pico-motor's ball bearing. And somehow this poor kinematic connection is drifting and slipping with the environment or something.
    - The v-groove of the item 7 in [1] carbide plate faces toward the pitch actuator, and away from the yaw actuator. While this is the right thing to do to prevent over constraint -- because the same part is used in both actuator interfaces, the ball of the pitch actuator (be it manual- or pico- driven) will sit "deeper" in longitudinal than the yaw actuator. The yaw actuators' stopper nuts all easily clear the movable mounting plate, but the pitch actuators do not.
   - The manually driven IXM100s show there's no issue, given that the cupped 8-100 alignment screw clears the carbide plate holes in the moveable optic-mounting plate.

ACTIONS FOR NEXT WEEK
We're at our wits end, and considering just ax'ing the picomotor actuation on M_B4 and M_M2. In fact, we've already replaced the mount of M_M2 with a manually driven IXM100, and may do so for M_B4 if we find enough clean IXM100 mounts.

However, we've got some ideas to fix the problem and still have remote actuation:
    - Place a washer between the carbide plate and the front plate.
    - Remove the stopper nut.
    - Mill away parts of the front plate.
    - Get a thicker carbide plate.
    - Use only one pico-motor per holder.

Pictures and further commentary to come in due time.
Comments related to this report
peter.fritschel@LIGO.ORG - 06:22, Saturday 30 May 2026 (90384)

If it's the stopper nut on the pico-motor, which seems pretty likely, then why not just screw it in further (away from the screw tip), rather than removing it? Seems much easier than removing it, or any of the other solutions suggested above, and in fact the 'using NF picomotor products' sheet says one shouldn't remove the stopper nut. Of course, if you don't actually need the remote actuation, better to just remove the pico's and replace with manual actuators.

brian.lantz@LIGO.ORG - 08:52, Friday 05 June 2026 (90498)

Fixed! see alog 90455 

several things fixed, esp NPRO

LHO VE (VE)
jordan.vanosky@LIGO.ORG - posted 14:17, Friday 29 May 2026 (90381)
HAM7 Vented, Doors Prepped for Removal

Jordan, Randy

HAM7 and the relay tube were vented this morning following venting procedures E2300169 and M1300464. RV1 remained closed along with FCV1 and FCV2, FC-A section remains under vacuum. 

Purge air particle counts were zeros, and the measured dewpoint at the HAM7 point of entry was -41.7C. Chamber was vented in ~2 hours to 780 torr, then the chamber was blown down to atmosphere ~762 torr.

Annulus ion pump was isolated, powered off and the annulus volume was vented using dry nitrogen.

After the chamber and annulus were vented, I wiped down the door flanges with IPA wipes, then Randy and I removed all but four bolts from the -Y door, +X door, and the 2x 12"CF blanks on the +Y door to be used for ISI access.

Will close WP 13283 once doors are removed next week.

Images attached to this report
H1 TCS
madison.simmonds@LIGO.ORG - posted 12:19, Friday 29 May 2026 (90380)
EY ALS ingoing and return beam measurements

Madi, Camilla, TJ. Repeating work at EX: 90370

Ingoing ALS beam measured between L6 and L7. Beam shape is better than at EX but still has strange astigmatic artefact.

Return beam arguably worse than at EX. Demonstrating the same lobed behaviour, with an overall 'peanut' shape.

Nanoscan head was tilted 45deg at each measurement point, to get comprehensive view of the beam. Both sets of measurements attached.

Pellicle beamsplitter has been left on table at EY.

Images attached to this report
H1 TCS
madison.simmonds@LIGO.ORG - posted 10:24, Friday 29 May 2026 (90370)
EX ALS ingoing and return beam measurements

Madi, Camilla, TJ

Recently been taking measurements of the ALS beam at EX, initially to observe the beam as it returns from vacuum. This was done using a Pellicle beamsplitter placed in the path of the ALS beam between the PBS and the LPM, which picked off the return beam for observation. Images from this measurement are attached. It was observed that the return beam was elliptical in shape, with two intensity peaks.
The input beam was also re-measured (previous measurements recorded here). It was seen that even the input ALS beam is elliptical in shape, and as it gets closer to the PBS, a lobed intensity pattern begins to appear. Considering the return beam is also elliptical with two lobes in the intensity pattern, the effects of the in-vacuum system are unable to be separated from the input beam characteristics, and limits our ability to use the ALS beam as a diagnostic tool for the in-vacuum path.

Also concerned for the performance of the ALS, that that the ALS beam is elliptical before going into the vacuum system. Potential future task will be to find out where the beam gains this ellipticity and correct it.

Images attached to this report
Non-image files attached to this report
LHO General
ryan.short@LIGO.ORG - posted 07:37, Friday 29 May 2026 (90378)
Ops Day Shift Start

TITLE: 05/29 Day Shift: 1430-2330 UTC (0730-1630 PST), all times posted in UTC
STATE of H1: Planned Engineering
OUTGOING OPERATOR: None
CURRENT ENVIRONMENT:
    SEI_ENV state: MAINTENANCE
    Wind: 17mph Gusts, 13mph 3min avg
    Primary useism: 0.02 μm/s
    Secondary useism: 0.29 μm/s 
QUICK SUMMARY: High winds last night that trigered some dust alarms that have since cleared. More HAM2 alignment work today in Laser HAZARD.

H1 IOO (IOO, ISC)
keita.kawabe@LIGO.ORG - posted 23:24, Thursday 28 May 2026 (90377)
IMC and IM2 alignment (Jennie, Elenna, Rahul, Keita)

https://alog.ligo-wa.caltech.edu/aLOG/index.php?callRep=90343

As per the plan in the above alog, we did the following for IMC and IM alignment.

As for clipping, before making IM changes, I installed an iris between IM3 and IM4 to see if the beam from PRM was retroreflecting.

Numbers and pictures will follow.

Will continue doing the IM3 and IM4 alignment tomorrow.

H1 PEM (PEM)
ibrahim.abouelfettouh@LIGO.ORG - posted 18:45, Thursday 28 May 2026 (90375)
Dust: Dust Monitor 10 on the rise

Just noticed DM 10 has been steadly going up for last 6 hours. So has the wind - could be an unpropped door? Just adding it here for log. Screenshot attached.

 

Images attached to this report
H1 SUS (SUS)
ibrahim.abouelfettouh@LIGO.ORG - posted 18:16, Thursday 28 May 2026 (90374)
BBSS QOSEMs Installed and Centering 50% Done

Ibrahim, Oli, Betsy

Today, we confirmed the BBSS Pointing with an oplev set-up using the M2 BOSEMs while the M1 BOSEMs were still on.

Then, we switched to cabling to prep for the QOSEM install. We installed the QOSEM flags and checked using the M2 BOSEMs and the OPLEV set-up that the pointing was unchanged. Thankfully, it remained the same.

Finally, we installed the QOSEMs onto the flags and began centering. We followed the procedure Oli and I wrote with Thomas' guidance on how to center QOSEMs - E2600219.

Before the end of the day, we were able to center:

We will return to it on Monday to finish centering. 

The QOSEMs were placed as followed (by SN):

F1 - S2600012 

F2 - S2600009 

F3 - S2600013

LF - S2600008

RT - S2600011

SD - S2600010

Attached is a sketch confirmation of our electronics for reference.

Images attached to this report
LHO General
ryan.short@LIGO.ORG - posted 16:32, Thursday 28 May 2026 (90373)
Ops Day Shift Summary

TITLE: 05/28 Day Shift: 1430-2330 UTC (0730-1630 PST), all times posted in UTC
STATE of H1: Planned Engineering
INCOMING OPERATOR: None
SHIFT SUMMARY: The LVEA was transitioned back to Laser HAZARD for more alignment in HAM2, work continued on the BBSS to switch it over to the new electronics setup, and prep began to open HAM7 among many other tasks done today.
LOG:

Start Time System Name Location Lazer_Haz Task Time End
14:36 FAC Randy LVEA - HAM7 cleaning 14:47
14:56 FAC Kim LVEA - Technical cleaning 18:10
15:15 SUS Betsy LVEA - Unplugging BBSS electronics 15:29
15:24 AOS Corey Opt Lab - Dropping off parts 16:08
15:33 VAC Travis MX, EX - Finish checking turbopumps 15:52
15:50 AOS Mitch, Randy, Corey LVEA - Getting baffles from BSC2 16:29
16:08 VAC Jordan LVEA - Corner RGA scans 16:50
16:16 SUS Fil LVEA - Moving BBSS cables near HAM3 17:20
16:23 VAC Travis LVEA - Checking CP1 pump 16:25
16:27 TCS Camilla EX - Retrieving camera 16:49
16:33 SPI Jeff Opt Lab Local SPI alignment 19:27
16:41 SUS Ibrahim, Oli LVEA - BBSS electronics 17:20
16:55 FAC Randy LVEA - Craning railings on BSC2 platform 17:48
16:57 SPI Jennie, Madi Opt Lab Local SPI alignment 17:54
17:20 SUS Ibrahim, Oli LVEA - BBSS work 19:09
17:26 SEI Jim, Shoshana H2 PSL - CRS building 19:18
17:37 IAS Jason LVEA - Grabbing FARO laptop 18:07
17:53 SUS Betsy LVEA - BBSS work 18:52
18:11 FAC Kim EX - Technical cleaning 18:54
18:39 SPI Jennie, Madi Opt Lab Local SPI alignment 18:57
19:10 SAF Keita LVEA YES Transition to HAZARD 19:18
19:29 ISC Keita LVEA Y HAM2 beam alignment Ongoing
19:29 SAF Laser HAZARD LVEA YES LVEA is Laser HAZARD Ongoing
19:31 ISC Rahul LVEA Y HAM2 beam alignment 23:29
19:47 ISC Jennie LVEA Y HAM2 beam alignment Ongoing
20:14 VAC Jordan LVEA - Restart corner RGA bakeout 20:23
20:19 FAC Randy LVEA - Looking for pallets 21:19
20:24 SPI Jeff Opt Lab Local SPI alignment Ongoing
20:29 SUS Oli LVEA/CER - QOSEM cabling/install Ongoing
20:46 SEI Jim, Shoshana H2 PSL - CRS building 21:44
20:48 SUS Betsy LVEA - BBSS work Ongoing
20:57 SPI Camilla Opt Lab - SPI optic cleaning 22:06
20:59 SUS Ibrahim LVEA - BBSS work Ongoing
21:16 SEI Mitch LVEA - Dropping off parts 21:25
21:17 VAC Jordan LVEA/CER - Prep HAM7 electronics for vent 21:42
22:31 TCS Camilla, Gerardo, Jordan Prep Lab - Building CHETA viewports Ongoing
22:53 VAC Travis MY - Cutting insulation Ongoing
23:11 SEI Jim LVEA - BBSS work Ongoing
LHO VE
jordan.vanosky@LIGO.ORG - posted 15:29, Thursday 28 May 2026 - last comment - 15:33, Thursday 28 May 2026(90371)
Prep for HAM7 Vent, High Voltage Disabled

Jordan, Travis

To prep for the HAM7 vent we followed the procedure M1300464 to disable the in vacuum high voltage sources and heating elements.

 

Comments related to this report
travis.sadecki@LIGO.ORG - 15:33, Thursday 28 May 2026 (90372)
Images attached to this comment
LHO VE (VE)
gerardo.moreno@LIGO.ORG - posted 08:34, Thursday 07 May 2026 - last comment - 19:17, Thursday 28 May 2026(90152)
CP1 Soft Regeneration Update

(Jordan V., Dave B., Gerardo M.)

The internal pressure to CP1 turned around overnight signaling that the process of emptying the trap is complete, now we'll continue to monitor and pump on the cryotrap volume.until good pressure is achieved.

A side note, I manually turned off the CC for PT114B last night at 9:44 pm (local time) as the pressure was rising a bit high, then turned it back on this morning at 5:33 am local time.

Attached is a snapshot of one day trend data of pressure behavior regarding the soft regeneration for CP1.

Process started here.

Images attached to this report
Non-image files attached to this report
Comments related to this report
gerardo.moreno@LIGO.ORG - 00:44, Wednesday 13 May 2026 (90220)VE

(Jordan, Travis, Gerardo)

CP1 soft regeneration update, CP1 pumpdown continues, system is currently pumped down by the SS500 cart, one turbo pump and one scroll pump.  Yesterday we visited the sensing line and we injected high purity nitrogen gas, we removed the lower sensing line near the Rosemount sensor to be able to inject the nitrogen gas, no issue introducing the gas, lower sensing line appears clear.

To be done, leak check CP1.

Attached is a plot of the pressure internal to CP1, the plot is for the total ongoing soft regeneration.

Images attached to this comment
gerardo.moreno@LIGO.ORG - 04:03, Thursday 14 May 2026 (90240)VE

(Jordan, Gerardo)

We leak checked CP1, specifically the bi-braze joints, we introduced He to both sensing lines (we disconnected the lines before the 3 way valve -X marks the spot - , this is less disruption to the shape of the metal tubing lines), we started with the bottom or low sensing line, we introduced 1 psi of flow into the line for about 35 seconds, no signal was detected by the leak detector attached to the exhaust of the turbo pump.  We did the same test with the high sensing line, no signal was detected.  Since we had the setup on hand we also decided to spray all the bellows, given that now they are free of ice, sprayed helium for about 35+ seconds, no signal was detected by the leak detector at any of the points sprayed.

During all the tests performed the He background at the leak detector was 1.0X10-10 Torr*L/Sec.

Images attached to this comment
gerardo.moreno@LIGO.ORG - 19:17, Thursday 28 May 2026 (90376)VE

CP1 pumpdown continues, no issues to report.  However, we had the aux-cart connected to the GV5 annulus trip, but we don't know how it happened, we noted only one tiny slithery critter around the area.

Attached is a plot of the total pumpdown.