Reset HAM3 and HAM4
The last successful diff locking was on Thursday May 8, alog 11791 on May 9. Below is a list of filter changes that happened on ETMX since then. The two suspects are: - L1 L2P filters - ETMX_M0_DAMP_L filters ===================================================== Date: -rw-r--r-- 1 controls controls 230237 May 9 23:29 H1SUSETMX_1083738611.txt ----------------------------------------------------- < # DESIGN ETMX_L1_DRIVEALIGN_L2P 0 zpk([0.08374528339909944-i*0.2433218667356948;0.08374528339909944+i*0.2433218667356948; ===================================================== Date: -rw-r--r-- 1 controls controls 237364 May 10 00:06 H1SUSETMX_1083740794.txt ----------------------------------------------------- > # DESIGN ETMX_L1_DRIVEALIGN_L2P 0 zpk([0.04672029281627461+i*0.3883629479048338;0.04672029281627461-i*0.3883629479048338; > # DESIGN ETMX_L1_DRIVEALIGN_L2P 1 zpk([0.01323117948903582+i*0.4349190738918082;0.01323117948903582-i*0.4349190738918082; > # DESIGN ETMX_L1_DRIVEALIGN_L2P 5 zpk([0.0837452833985204+i*0.2433218667356947;0.0837452833985204-i*0.2433218667356947; < # DESIGN ETMX_L1_DRIVEALIGN_L2Y 0 zpk([0.04309093963903244+i*0.3314665390167811;0.04309093963903244-i*0.3314665390167811; < # DESIGN ETMX_L1_DRIVEALIGN_L2Y 1 zpk([0.3079048301517223;0.4191165157453778], ===================================================== Date: -rw-r--r-- 1 controls controls 237364 May 10 00:27 H1SUSETMX_1083742050.txt ----------------------------------------------------- ===================================================== Date: -rw-r--r-- 1 controls controls 230526 May 10 00:42 H1SUSETMX_1083742948.txt ----------------------------------------------------- < # DESIGN ETMX_L1_DRIVEALIGN_L2P 0 zpk([0.04672029281627461+i*0.3883629479048338;0.04672029281627461-i*0.3883629479048338; < # DESIGN ETMX_L1_DRIVEALIGN_L2P 1 zpk([0.01323117948903582+i*0.4349190738918082;0.01323117948903582-i*0.4349190738918082; < # DESIGN ETMX_L1_DRIVEALIGN_L2P 5 zpk([0.0837452833985204+i*0.2433218667356947;0.0837452833985204-i*0.2433218667356947; ===================================================== Date: -rw-r--r-- 1 controls controls 230526 May 10 01:32 H1SUSETMX_1083745955.txt ----------------------------------------------------- ===================================================== Date: -rw-r--r-- 1 controls controls 246604 May 10 03:42 H1SUSETMX_1083753759.txt ----------------------------------------------------- > # DESIGN ETMX_L1_DRIVEALIGN_L2P 0 zpk([0.831329491504266+i*0.9012257170546942;0.831329491504266-i*0.9012257170546942; > # DESIGN ETMX_L1_DRIVEALIGN_L2P 1 zpk([0.002485877643515575-i*0.3946128198094371;0.002485877643515575+i*0.3946128198094371; > # DESIGN ETMX_L1_DRIVEALIGN_L2P 5 zpk([0.08374528339823091+i*0.2433218667356947;0.08374528339823091-i*0.2433218667356947; > # DESIGN ETMX_L1_DRIVEALIGN_L2Y 0 zpk([0.05841220204334667+i*1.127241260196624;0.05841220204334667-i*1.127241260196624; > # DESIGN ETMX_L1_DRIVEALIGN_L2Y 1 zpk([-0.2851704563409714-i*0.2165396550111315;-0.2851704563409714+i*0.2165396550111315; > # DESIGN ETMX_L1_DRIVEALIGN_L2Y 5 zpk([0.04309093963845343+i*0.3314665390167811;0.04309093963845343-i*0.3314665390167811; > # DESIGN ETMX_L1_DRIVEALIGN_L2Y 6 zpk([0.3079048233615395;0.4191165225355606], > # DESIGN ETMX_M0_DAMP_L 2 butter("BandPass",4,0.1,5) > # DESIGN ETMX_M0_DAMP_L 3 resgain(0.43,5,4)resgain(0.99,5,4)resgain(1.98,5,4)resgain(3.4,5,4) ===================================================== Date: -rw-r--r-- 1 controls controls 245257 May 10 03:56 H1SUSETMX_1083754591.txt ----------------------------------------------------- < # DESIGN ETMX_M0_DAMP_L 2 butter("BandPass",4,0.1,5) < # DESIGN ETMX_M0_DAMP_L 3 resgain(0.43,5,4)resgain(0.99,5,4)resgain(1.98,5,4)resgain(3.4,5,4) ===================================================== Date: -rw-r--r-- 1 controls controls 249180 May 12 10:15 H1SUSETMX_1083950161.txt ----------------------------------------------------- > # DESIGN ETMX_L1_DRIVEALIGN_L2P 4 zpk([0.831329491504266+i*0.9012257170546942;0.831329491504266-i*0.9012257170546942; < # DESIGN ETMX_L1_DRIVEALIGN_L2Y 5 zpk([0.04309093963845343+i*0.3314665390167811;0.04309093963845343-i*0.3314665390167811; > # DESIGN ETMX_L1_DRIVEALIGN_L2Y 5 zpk([0.04309093963816393+i*0.3314665390167811;0.04309093963816393-i*0.3314665390167811; < # DESIGN ETMX_L1_DRIVEALIGN_L2Y 6 zpk([0.3079048233615395;0.4191165225355606], > # DESIGN ETMX_L1_DRIVEALIGN_L2Y 6 zpk([0.3079048301514328;0.4191165157450882], ===================================================== Date: -rw-r--r-- 1 controls controls 245252 May 12 10:26 H1SUSETMX_1083950783.txt ----------------------------------------------------- < # DESIGN ETMX_L1_DRIVEALIGN_L2P 4 zpk([0.831329491504266+i*0.9012257170546942;0.831329491504266-i*0.9012257170546942; ===================================================== Date: -rw-r--r-- 1 controls controls 237890 May 12 10:36 H1SUSETMX_1083951424.txt ----------------------------------------------------- < # DESIGN ETMX_L1_DRIVEALIGN_L2P 0 zpk([0.831329491504266+i*0.9012257170546942;0.831329491504266-i*0.9012257170546942; < # DESIGN ETMX_L1_DRIVEALIGN_L2P 1 zpk([0.002485877643515575-i*0.3946128198094371;0.002485877643515575+i*0.3946128198094371; < # DESIGN ETMX_L1_DRIVEALIGN_L2P 5 zpk([0.08374528339823091+i*0.2433218667356947;0.08374528339823091-i*0.2433218667356947;
I've swapped the network connections for the DMT machines to a new switch as per WP4622, this is in part to make more room in the rack for additonal equipment. As far as I can tell, it looks like everything still works...
no restarts reported.
Added a ZFL-500HLN amplifier to the ALS DIFF RF path.
Alexa and I found that this amplifier was not working, so we removed it.
The amplifier on DIFF was not working because we had input/output backwards. I have installed another amplifier on DIFF. I have also put a new amplifier on COMM (HNL) that piggy-backs the power from the BBPD; this amplifier has slightly less gain (about +24dBm in comparison to +30dBm), so we expect about -7dBm for the beatnote.
We are investigating the Z to RZ couplings that are currently limiting our ability to improve the Yaw isolation.
A measurement was performed on ITMY yesterdaty night. The unit was controlled with level 3 controlers and high blend (T750mHz) in all 12 degrees of freedoms.
It has been driven at the Exc point of the Stage 1 Z isolation filter, therefore the drive was in [nm]. A white noise drive was used (filtered to put power on the low frequencies)
The plot attached shows the reponse of the inertial sensor. The top plot (Stage 1 T240s) are in [nm/s], [nrad/s] per unit of drive [nm]. The bottom plot (Stage 2 GS13s) are in [nm/s^3], [nrad/s^3] per unit of drive [nm].
The Z, RX, and RY response are as expected: slope goes as f, large main coupling, cross coupling at sub-percent level...
X, and Y couplings are in high in the T240s, but suprinsingly the coherence is not very good.
As for RZ, which is the main focus of this measurement:
- the T240s show a 1/f slop that we assume is due to magnetic couplings
- the GS13s shows the f^3 slope as expected, confirming the signal on the T240 is likely not real motion.
We have set up a measurement in the staging building to measure the direct coupling from one actuator to the T240s.
Just started a similar measurement on ITMY, with all isolation loops off except Stage 1 Z and Stage 2 Z that is still on.
Jeff will stop the measurement when the maintenance adctivites start on this unit (I will be in the staging building for the direct coupling measurement)
Here are the results with only the Z loops engaged. The X and Y and couplings are much higher, presumably because of higher tilt-coupling when the RX and RY isolation loops are off. The coupling with all other degrees of freedoms is essentially unchanged.
Earthquake tripped ISIs last night, looks like it's the one off the coast of Oregon 5.1 @ 10km.
Install Activities:
- TCS Team is going to work on HWS table until 2 PM and then go to laser hazard and align the CO2Y table, CO2X's overnight run looks like its working well.
- HAM5 SR3 alignment is ongoing with Jason and Jeff. After they're done with the alignment, fine adjustments and transfer functions will begin.
- Margot and Travis are working on ACB assembly, Mitch gave a hand yesterday but he might be working with SEI today
- Staging building work is ongoing with SEI team with help from Scotty from Apollo. Fabrice wants to take magnetic coupling measurements.
- ESD work is ongoing, both end stations have their various problems. The problem could be in-vacuum and might need the June vent to fix although the problem has not been precisely determined yet.
- Integration is ongoing, some progess last night but a few problems.
- During June-July vent, it's probable that we'll be implementing wire-hung baffles on BS and an ISS on HAM2
Maintinence:
- LN2 @ EX
- Jeff Kissel is going to implement new SUS code
- Christina and Terry are going to take stuff off-site
Find attached the watchdogs trips summary of last week/beginning of this week.
Nothing unusual to report, except one specific trip on ISI-ETMY, where we can see some "glitchiness" in the drive. I've noticed the same behavior on this unit two weeks ago. We're still investigating.
I've added 10.22.0.0/20 to the ufw rules on vxboot to allow ssh.
I've rebooted cdsfs0 to perform the work specified in WP4620. To wit, available OS patches were applied and the NFS options for rpc.mountd were changed to allow the proper operation of group permissions on /ligo (specifically, --manage-gids was removed from RPCMOUNDOPTS in /etc/defaults/nfs-kernel-server).
NOTE: This means that group permissions should now operate correctly on /ligo should you wish to use them to share files.
Here is the list of commissioning task for the next 7-14 days:
Green team (XY-arm):
Blue team (X/Y-arm):
Red team:
SEI/SUS team:
Arnaud, Alexa, Sheila, Kiwamu,
Tonight we tried closing the ALS diff loop, but it did not go well. We observed a high peak at 1 Hz, which we don't understand and seems to prevent us from going back to the high UGF configuration that we achieved in the last week. Since we ran out our energy at this moment, we will have a close look tomorrow. This may be a gain peaking , a bad cross over or some stupid reason.
We tried increasing the servo gain to the nominal value (which should give a UGF of 4 Hz), but today we were not able to reach that point due to the instability at 1 Hz. So we mostly worked with a lower UGF by a factor of 3 or 4 at which the loop was relatively stable. Changing the TST gain did not seem to help. The attaches s the in-loop error signal (show in red) and free-running noise (in black). When we closed the loop, a oscillation happened at 1 Hz. Hmmmm.....
A good new is that Sheila succeeded in deploying a guardian for the ALS diff control. So it now allows us to keep track of good settings.
Fabrice's measurement is started on ITMY, running on operator1
After Sheila saw some excess angular motion caused by the length drive, I tried improving the decoupling of EX and EY UIM.
[Keita Arnaud]
Measurements live in /ligo/svncommon/SusSVN/sus/trunk/QUAD/H1/ETMX/SAGL1/Data called 2014-05-13_H1SUSETMX_L1_{L/P}2PY.xml
D. Hosken, G. Grabeel, T. Vo Today we wanted get the CO2X laser table in a position to run the closed system overnight. We've taken some extensive precautions using redundant beam dumps along the laser path to make sure that we don't have stray beams and that the main laser beam does not get into the vacuum system via the periscope. Beam dump locations: - After the output beamsplitter - Secondary beam dump after the final steering mirror - A shield between the second iris and the first periscope mirror The rotation stage was power-cycled to see if we could reproduce the errors that M. Heintze saw last week but we couldn't get the same behavior. I also forced the Motor Warning label to be "FALSE". We've left the rotation stage close to minimum power with about 2.2 Watts going through after the polarizers so we can monitor the beam power down stream with an on-table power meter that should be reading ~.199 Volts (working but not yet calibrated). We expect it to go up and down a bit because of the temperature fluctuations and we left PZT/Chiller loop open. The jumper for the interlock for the rotation stage is removed so that no one in the control room can rotate the HWP via EPICS. We've left the HEPA and the lights off at 6:00 PM PT, The table is locked and we've tagged out the keys and left them in the control room box with our phone numbers attached. ISS PD adjustments: We removed the covers and beam dump to let light onto the ISS PDs. We also translated the PDs back ~2-3 mm back and fine-tuned the alignment onto the center of the PDS. Temperature Sensors: The temperature sensors were not working very well at first. There were only 2/6 working which turned into 1/6 as we were trying to troubleshoot. Turns out that the problem was due to a loose connection at the feedthrough, once we tightened the connector screws, everything worked pretty well. We'll be monitoring these temperatures quite closely during the overnight observation because it'll give us a first-look indication if anything is wrong. H1-TCS-C_CO2_X_TEMPERATURESENSOR1 = AOM H1-TCS-C_CO2_X_TEMPERATURESENSOR2 = PLUMBING MANIFOLD H1-TCS-C_CO2_X_TEMPERATURESENSOR3 = AOM DRIVER H1-TCS-C_CO2_X_TEMPERATURESENSOR4 = WATERCOOLED BEAM DUMP H1-TCS-C_CO2_X_TEMPERATURESENSOR5 = RF DRIVER
This morning the end Y laser was off and had no power, Richard looked around and noticed that there was an extension chord which had come loose. He changed the way that this is plugged in so this should not happen again.
Alexa and I placed the GigE camera on ISCT1 for the X arm.
I also went out to End Y a few times to work on the IR path there. The LSC PD is now aligned for the IR trans, the gain setting is 60dB. The power cable is flaky for the analog camera. Aaron and Fil helped get the signal to the control room. Although the spot is faint you can see it in the upper right hand corner of channel A on the lower monitor.
After Richard fixed the issue with the ETMX ESD (see alog 11573) this morning, I briefly took an angular transfer function of pitch and yaw using the oplev. They don't look crazy -- 1/f^2 shape and non-measurable crosscoupling between pitch and yaw. However there was a descrepancy from the model predictions by a factor of 2-ish. I am not sure what makes the descrepancy for the moment. The transfer functions are shown below with the models for comparison.
Anyway, the ESD is functional and ready to go.
Note that I included Jeff K's arc-integral-factor which gave an extra factor of 2/pi for the torque in the model. For those who are interested in the details of the calculation, please find it in the attachment (ESD_pitandyaw.m). The raw data are attached as well.
The L1 ESD actuation measurements, applying 2 Hz pitch and yaw signals and looking at the optical lever signals, also show the reponse being a factor of 2 smaller than expected. There seems to be something systematic here that we are missing.
The original templates for this measurement can be found here: /ligo/home/kiwamu.izumi/Desktop/binary/20140424_ESD_ETMX/dtt/ swept_sine_long.xml (for L2L) swept_sine_pit_yaw.xml (for P2P and Y2Y) In addition, they've been copied and committed to the SUS repository here: /ligo/svncommon/SusSVN/sus/trunk/QUAD/H1/ETMX/SAGL3/Data/ 2014-04-28_H1SUSETMX_L3_L2LPY_SweptSine_1to20Hz.xml 2014-04-24_H1SUSETMX_L3_P2PandY2Y_SweptSine_1to20Hz.xml
i made those changes. M0_DAMP_L filters were loaded in FM2 and FM3 to do a quick test on friday, and have been removed right after. The usual damping filters are still loaded in FM0/FM1 as previously so no actual config change for damping. Actual change is that we were running with new UIM L2P filters for ETMX/ETMY, and L2Y filters not engaged.