Valved-out, removed, cleaned, adjusted and reinstalled. Valved-in -> Working OK now. No interruption to purge air supply
We've found two discrepancies between the ADC/DAC channel assignment document T1100472 and the end station ISC wiring document D1100670. After some discussion, we decided that the right way to proceed is to change the channel assignment in the model and update T1100472. The model was already updated but the document is yet to be done. Physical wiring was not changed at this time.
1: CM boards fast readback channel assignment
We have two CM boards at the end station, one for PLL and one for PDH, and the fast readback looked like they were swapped.
According to the wiring diagram, the first CM board is PLL and the second one is PDH. Which means that the PLL CM board uses the first ADC DB9 input for AA for ADC 1 and PDH uses the second. Physical wiring as well as slow control follows this convention.
OTOH, the channel assignment document says that DB9_1 for ADC1 is used by PDH and DB9_2 is PLL. h2iscey model follows this.
We decided to change the channel assignment so everything agrees with everything.
2: Misc. diodes DC fact readback channel assignment
There are two kinds of photodiode DC output, one is the DC of the legacy iLIGO RF diode and the other is the output of generic diodes (e.g. PDA 100A) via the new aLIGO generic tabletop interface.
In the wiring diagram, the legacy output is not connected to the fast readback at all. The generic interface is connected to the third DB9 of AA input for ADC1.
In the channel assignment document, DB9_3 for ADC1 is used by the iLIGO RF diode (PDH_DC) and the generic interface uses DB9_4.
We decided to leave the physical wiring alone, but swap the channel assignment (i.e. DB9_3 for generic and DB9_4 for legacy) in the model.
Each DB9 holds up to four channels, and before the model change DB9_3 and DB9_4 used to hold a total of 4 channels.
After the change, each of these have 4 channels.
In DB9_3, PD1 is the new channel H2:ISC-ALS_EY_REFL_PWR_MON (which is a diode in the Hartman WFS path). Three old channels that already existed were shifted by one slot (PD2=red power monitor, PD3=green power monitor, PD4= PLL DC power).
In DB9_4, we have four channels (PDH DC, AUX1, AUX2 and AUX3 in this order). AUX channels are new (but PDH DC was not available in reality anyway, because there was and is no physical connection to the AA, it was/is only connected to Beckhoff). We need another cable going from the field to the AA chassis to actually use these four channels.
With the help of the SUS folks, I increased by a factor of 3 the gain on the quad yaw and vertical (both M0 and R0 on ITMY and ETMY). I also added 0.45Hz boosts to L and T for the transmon damping. All of these changes are aimed at making sure that the ISI does not see sharp resonant features from the suspensions.
I started the evening with the PLL unlocked, and the cavity badly aligned. The cavity alignment problem came from the HEPI, which had tripped and thus let go of its 1M count RZ offset. It turns out to be surprising difficult to restart HEPI without the watchdog tripping;
Or maybe we should just consider making the WD less sensitive.
The PLL was not working because the CM board was not set properly. The compensation filter was off, and the boost was 1. I guess these should be {on, 0}, or at least it works like this. Similarly the PDH CM board had the common option on, which made it not work either. We should really find a better solution.
After fixing these problems, and tweaking the alignment with the ITM and ETM, the cavity locked and was very stable. We should check the state of the ISIs during this time.
Plot requested by Jeff K.
boost=1 and no comp for PLL means that something/somebody attempted to copy the PDH CM setting to PLL.
But PLL was left locked when I went home. There's no good reason the setting should/could have changed. Puzzled.
After a false start wich for some reason tripped the watchdogs, I managed to start the driven tests on the ISI around 12am local time. The HEPI was also tripped... I'm not sure if this happened before the ISI tripped, or because it tripped. Please check filters and switches on the ISI isolation filter banks, as they seemed to be in an odd state.
These are some reference data from a long lock on the weekend. There are 3 hours of continuous lock between 14:00 and 17:00 UTC (2012-07-08). The long locks show a full tidal cycle; 1450 counts on the BOSEMS sensors ~ 580um ~ 50k counts of drive at the top mass. It also shows very little residual L2Y coupling, and a little L2P (which I later tried to remove with an L2P coefficient of 3e-4).
Attached are plots of dust counts > .5 microns in particles per cubic foot.
The continuing tales of HAM6 purge have found the lonely ISI near the end of adventures ... Or is it‽ The dew point numbers seem to be hanging out at the -32 range for the most part. I'm going to turn the flow rate up to 15-20 liters/minute and see if this will urge another drop.
Thomas V. Szymon S. John W. We installed the receiver enclosure fully with the viewport protector, reducer (temporary, used from ILIGO) and bellows. During the transmitter enclosure installation, John noticed that we are extremely close to the bare viewport, approximately 3.75 inches between the enclosure face and the viewport. There isn't enough room between the enclosure and the viewport to fully fit the standard protector, reducer and bellow. For the one arm test sake, a possible makeshift connection might be made. More work on this to continue.
Dave and Jim
The problem of the missing H1 test points was tracked down to a configuration issue in the core switch. The entry for the OPS VLAN needed to have the H1 subnet added to permit the UDP broadcast routing onto the H1 FE LAN.
Now low level test points diagnostics will show both H1 and H2 AWGTP processes. We discovered that h2pemeyaux was using a duplicated DCUID as h1sush34. We have powered down h2pemeyaux for now, and will give it new DCUID numbers during tomorrow's Tue Morning Maintenance.
Greg Mitchell & Hugh Back on Friday a week ago, the SEI was floated on HEPI and then locked down, see aLog 3315. Today we released the stops and adjusted the HEPI springs to level the Optical Table. We are very close and basically ready for horizontal adjustments in response to IAS. *** The Table remains free and is floating ***
J. Kissel, P. Fritschel After all the investigations into the SUS loop performance to find the source of the excess motion Pitch and Longitudinal motion at 0.43 (, 0.56, and 1.0) [Hz], Peter suggested perhaps it's merely the expected coupling between L and P, with the large not-yet-awesome input motion from the BSC-ISIs. So, following the same prescription used to generate the curves in G1200712, I produced the predicted QUAD test mass motion due to the measured (BSC8-ISI, ITMY) motion on June 26th, i.e. E1200668, in both L and P. Attached are the results. We see that indeed, given the (BSC8-ISI, ITMY) input motion, the predicted motion is on the order of 2.4e-6 [m RMS] and 5e-6 [rad RMS], with the expected first L and P modes at 0.43 Hz and 0.56 Hz, which have (modeled) damped amplitudes of 1e-5 [m/rtHz] and 2e-5 [rad/rtHz], reasonably consistent with results reported in LHO aLOG 3363, LHO aLOG 3302, and LHO aLOG. There are several ways in which this model isn't perfect: - The input motion is representative of BSC8-ISI (ITMY), which has been commissioned further than BSC6-ISI (ETMY), so one might expect the input motion to ETMY to be somewhat worse (It only has damping, No HEPI, No Level 0 Isolation Loops). Fabrice is working on getting me BSC6 data. - I took the input motions in X, Y, Z, RX, RY, and RZ -- which are defined about the center (in X and Y) of the ISI, and at the lower-zero-moment-actuation-plane of ST2 of the ISI -- as direct inputs to the suspension point of the QUAD: (Y->) L, (X->) T, (Z->) V, (RY->) R, (RX->) P, (RZ->) Y, which means that the estimate for P does not account for the ~0.5 [m] lever arm between the ISI ST2 origin and the SUS point origin. See T1100617 for details (B. Lantz, C. Kucharcyzk, and I are working on getting the correct transform.) The bonus attachments, relevant to the discussion, are as follows - [2012-07-09_testmassmotion_bscinput.pdf] A plot of the motion used as input (identical to what is shown in E1200668) - [2012-07-09_modeltf_*toP.pdf] The rarely-looked-at transfer functions between all degrees of freedom input to pitch in [rad/m] or [rad/rad]. - [2012-07-09_testmassmotion_P_resgndbudget.pdf] A break down of the predicted residual P motion from all degrees of freedom. One VERY interesting revelation from these bonus plots: - T @SUS point transmission to P @ test mass becomes comparable to L to P in [rad/m] above ~1 Hz - R @SUS point transmission to P @ test mass becomes roughly a factor of 10 greater to P to P in [rad/rad] above ~0.5 Hz These mean we'll have to focus on reducing the T and R motion *just as much* as reducing the L and P motion.
HAM-ISI Unit #6 was balanced, and CPS readouts were within acceptable range, on 07/03 when we left it for long TF measurments. When checked this morning, CPS readouts featured an offset of approximately +/-3000 counts:
|
|
07/03 |
07/09 |
Difference |
|
H1 |
-387.82 |
2014.8 |
2402.62 |
|
H2 |
-15.363 |
2259.8 |
2275.163 |
|
H3 |
291.12 |
2534.3 |
2243.18 |
|
V1 |
-80.917 |
-3112.1 |
-3031.183 |
|
V2 |
-38.773 |
-3118.5 |
-3079.727 |
|
V3 |
119.34 |
-3054.5 |
-3173.84 |
There is no drive/offset on MEDM channels.
Coil drivers were turned off. The CPS readouts remained unchanged.
CPS interface chassis were turned off, and then turned back on. The CPS readouts remained unchanged.
Dataviewer plots are attached. They show the drifting of the CPS readouts.
We experienced high temperatures over the last few days.
| 3-Jul | 9-Jul | Difference | |
| H1 | -387.82 | 2014.8 | 2402.62 |
| H2 | -15.363 | 2259.8 | 2275.163 |
| H3 | 291.12 | 2534.3 | 2243.18 |
| V1 | -80.917 | -3112.1 | -3031.183 |
| V2 | -38.773 | -3118.5 | -3079.727 |
| V3 | 119.34 | -3054.5 | -3173.84 |
| 3-Jul | 9-Jul | Difference | |
| H1 | -387.82 | 2014.8 | 2402.62 |
| H2 | -15.363 | 2259.8 | 2275.163 |
| H3 | 291.12 | 2534.3 | 2243.18 |
| V1 | -80.917 | -3112.1 | -3031.183 |
| V2 | -38.773 | -3118.5 | -3079.727 |
| V3 | 119.34 | -3054.5 | -3173.84 |
The ISI was re-blanced this morning. Reasonable values were obtained along Z.
However, re-balancing the ISI did not correct the out-of-specification offset observed on horizontal CPSs.
CPS readouts, after re-balancing this morning, are presented below:
| H1 | 1901.6 |
| H2 | 2268.7 |
| H3 | 2417 |
| V1 | -34.45 |
| V2 | 47.896 |
| V3 | -201.18 |
In order to get a better understanding of what was happening, we collected data from GS13/L4C pressure sensors. Data shows:
Notes:
The ISI was locked. CPS readouts are within expected range.
| H1 | -348.96 |
| H2 | 297.36 |
| H3 | -156.01 |
| V1 | 252.29 |
| V2 | 155.3 |
| V3 | 323.62 |
The drifting we observed was not caused by a malfunctioning of the CPSs.
We later found that one circuit of our air conditioning had failed and therefore we could not maintain normal conditions in the staging building. There is no record of the indoor temperatures during this event but I estimate that the temperature excursions were on the order of 5-10 degrees F. Normal excursions (night-day) are probably 2-3F and perhaps closer to 1F during the day only (if you exclude the cooling overnight.
I started this fine Saturday checking the PZT alignment loops while JeffK measured SUS TFs. The idea was to make sure that the loops were fast enough to ensure that sub-Hertz alignment loops would not be bothered by sluggish PZT response. I found all of the loops in good working order with UGFs between 3 and 10Hz. While I was there I added cut-off and boost filters (loops are still unconditionally stable) and set all the UGFs a little closer to 10Hz.
In search of something to blame for our large angular motion, much of which appears at 0.43Hz (the first longitudinal resonance), I measured the Transverse loop (side OSEM), which also has a resonance around 0.43Hz. It wasn't doing much, so I broght it up to speed with the Longitudinal loop boost filter. I also changed the cut-off somewhat, as there was very little phase margin for the highest resonance (near 4Hz). The result was a much more damped T DOF, but not much else that was obvious.
After figuring out that the PHASE and PDH fast monitor signals are switched in digital land, I was able to close a slow loop (< 100mHz UGF) which off-loads the VCO signal for locking the arm cavity to the ETM. At the moment, the locking filter is in the SUS-ETMY_M0_LOCK_L filter bank rather than the ALS_EY_ARM_LONG bank. This is because ETMY_M0_LOCK_L_IN1 is recorded at 2kHz, which is useful for making spectra (see below).
By stepping the gain of the slow loop after a large output had accumulated (with the input switch off), I was able to modulate the length of the cavity without unlocking. This modulation is visible in the signal send to the VCO for cavity locking, and in the ETMY M0 OSEMS, so I cross-calibrated teh VCO signal using 40nm/cnt as round number for the OSEMS (see fig 1). This gave 0.8nm/cnt for FMON, which might be 40kHz/V for the VCO if I got all of my conversions right... not so far from the 100kHz/V I would have guessed. I made 3 spectra from locks separated by ~1 hour, all of which overlap nicely (see fig 2).
The main threat to lock stability was a large Long -> Yaw coupling that would misalign the cavity as the slow length loop pushed on ETMY_MO_LOCK_L. I fixed this with a small element in the drive align matrix (L2Y gain = 0.0036), indicating that we will probably have this problem with all of the suspensions just due to small magnet strentgh mismatches and BOSEM misalignments. With this in place, the cavity will stay locked for hours with ~10% power flucutions (see fig 3, 4). For reference, I include the alignment slider values in fig 5.
Calibration could be (and probably should be) done in the opposite direction, from VCO frequency/volt calibration to displacement.
M. Evans, (J. Kissel) Just because we may (read: will most definitely) have to do it again, I called Matt and asked "How'd you come up with that 0.0036 L2Y coefficient for the DriveAlign Matrix?" Here's what he did: - Look at DC Y Value (in DAMP IN1) with no L offset. (Say it's 1000 cts) - Put a Huge L offset in place (through the TEST filter bank, for example), and watch Y change. - Put a number into the L2Y DriveAlign matrix, and tweak until DC Y Value returns to what it was before Huge L offset. Done! Easy-peezy, Japanese-y. For the record, he says he also has a coefficient in place for L2P, but "[he's] not sure it's doing anything."
The "calibrated spectrum" shown above does not include a 1.6:40Hz pole:zero which are in the VCO. Doing this correctly will cause the spectrum to slope down between 1.6 and 40Hz... next time we'll include this, as well as the direct VCO calibration that Keita suggests.
To clear up some confusion, everything was conforming to one document or the other. It's not like something didn't agree with any document.
Field wiring and Beckhoff model was made according to the wiring diagram.
ISC frontend was made according to the channel assignment document.