kyle.ryan@LIGO.ORG - posted 16:02, Thursday 31 March 2011 (675)
X-end instrument air alarm
"Lead" pressure switch is failing on X-end instrument air compressor.  "Lag" switch is ok -> Will replace bad part tomorrow.  For now, I made an adjustment which should lessen the nuisance alarms overnight barring a complete component failure.  The temporary norm will be for lower than normal PT599 values overnight.  
H2 General
dani.atkinson@LIGO.ORG - posted 13:26, Thursday 31 March 2011 (674)
ALS Enclosure Modifications
I've been modifying the ALS enclosure (for the one-arm test) as our test case for modifying all ISC enclosures for adLIGO. The work is mostly done; as illustrated below, patch panels and small exhaust louvers have been added (made of aluminum, and with no clear optical line-of-sight) to the sides and the enclosure panels modified accordingly. The top of the enclosure has been altered to accommodate a 2'x3' HEPA fan filter (not yet wired). Cable trays and shelves are suspended near the top of the inside of the enclosure, freeing table space previously used for running cables. The panels on back which had periscope holes drilled have also been replaced with fresh panels, so the new periscopes can be positioned as need be.

Still left to do:
  • Implement laser safety locks on enclosure (still under discussion).
  • Add and wire interior lighting.
  • Wire up HEPA and test flow.
  • Add acoustic insulation back to replaced panels if needed.
Images attached to this report
H2 DAQ
david.barker@LIGO.ORG - posted 11:42, Thursday 31 March 2011 (673)
CDS upgrades and training

CDS training continues today, mainly in the control room. We are upgrading code on the H2 system, so these computers are being rebooted.

H2 General
jonathan.berliner@LIGO.ORG - posted 21:07, Wednesday 30 March 2011 (672)
Wednesday Ops Log
- CDS tutorial began today.
- De-grouting work continues under H2 input optics tube area.
- EPICS channels from chiller yard aren't functioning.  Apparently, this has been the case for a while, but I didn't realize it.
- David Nolting convenes weekly safety meeting.
LHO FMCS
mark.lubinski@LIGO.ORG - posted 15:44, Tuesday 29 March 2011 (671)
Well Pump
Ran well pump twice today.  King Soft Water out for monthly service and water check.
H2 General
michael.rodruck@LIGO.ORG - posted 15:41, Tuesday 29 March 2011 (670)
Ops Day Summary
H2 General
jonathan.berliner@LIGO.ORG - posted 16:55, Monday 28 March 2011 (669)
Monday Ops Log
- Filiberto out to MX/MY to grab boards for Daniel Sigg.
- HEPI installation continues in Biergarten.
- Projector2 (itself, not the server) is out of operation. Patrick Thomas is investigating.
- A Windows machine on the CDS network was errantly sending many repeated requests to the DCC server at Caltech, inviting attention from admins at Caltech and LHO.
- (269) 978-1229 called twice, purporting to be from "Google" about updating our site listing.  It seems to be telemarketers who are not affiliated with Google.
- Swagelok delivery for Hugh Radkins.
- Crew begins to arrive for CDS aLIGO training later this week.
- Ochoa Middle School (Pasco, WA) tours the site.
H2 INS
greg.grabeel@LIGO.ORG - posted 16:52, Monday 28 March 2011 (668)
BSC 7 HEPI Status
BSC 7 now has all of the HEPI Assemblies installed. The South West corner saw the need for the HEPI foot position to be adjusted slightly relative to the HEPI frame.

The bottom clamps that had the bent screws have all been replaced with the HoloKrome Carbon steel screws. New torque values were used as well for all of the 1/2-13 and set screws.
Images attached to this report
H2 INS
michael.landry@LIGO.ORG - posted 11:18, Monday 28 March 2011 (667)
HAM12 in-chamber cleaning status
Summary:

On Thursday Mar 24th, we made an attempt to fully wire-brush and sample inside iLIGO HAM12 (aLIGO HAM11).  We were partly successful in that 2/3 of the chamber is now wire brushed, and we believe the procedure outlined in T1000725 will form the baseline for cleaning fully the H2 diagonal envelope, and later, L1 and H1 volumes. However in the process we erroneously made use of a screw-type air/oil compressor which may have contaminated some interior surfaces of the chamber.  FTIRs were taken and are due back Thu Mar 31. They will inform of a solution for how to proceed with this chamber.

Some details:

Setting out to wire brush the iHAM12 interior, we defined a matrix for interior surfaces of the chamber and began wire brushing the roof.  This work is ergonomically taxing, requiring sufficient person-power in-chamber, and short shifts of about 5 minutes each, particularly when overhead.  The original (clean) compressor supplying the pneumatic tool was found to decay in air-pressure, inducing delays while the compressor regenerated, so we opted to acquire another, larger capacity unit. This second compressor (Atlas Copco XAS 185) is a screw compressor in which the pump unit employs oil in the screws and then separates it out, and cannot be employed for our clean in-chamber work.  Running the pneumatic tool with the new compressor for 20-30min yielded a failure of the tool (not unexpected as that tool had integrated ~1hr worth of activity). When inspected, oil mist contamination was noted in the tool, the operation was shut down, FTIR samples were taken of both the areas that were brushed with the clean compressor, and the two areas (approx 4 square feet each) that were cleaned with the dirty compressor.  We have ceased operations on iHAM12 and will do no more tests until any further mitigation steps are decided upon; additional assays may be required.  Hoses and garb from Thursday's cleaning operation are quarantined, as are the vacuum.

More details and pictures in a follow-up alog.
LHO FMCS
dani.atkinson@LIGO.ORG - posted 16:04, Friday 25 March 2011 (665)
Ops Day Shift Summary
  • Further HEPI assembly at BSC7.
H2 INS
corey.gray@LIGO.ORG - posted 16:03, Friday 25 March 2011 (664)
BSC7 HEPI Status

[Corey, Greg]

SW Location (s/n 77)

A job we hope would be a one hour task turned into a day long endeavor (which is still ongoing).  Yesterday afternoon Greg drilled and tapped holes on the Pier (after the iLIGO Actuation Stack was removed).  This morning we hoisted the new HEPI Assy onto the Pier and discovered that the Support Bracket holding it was an unmodified one, and we had interference issues(!). 

So we lugged the HEPI Assy down to the ground and for safety/alignment reasons, re-installed the iLIGO Actuation Stack. 

We then went to the NE HEPI, confirmed all the HEPI Foot clamping bolts were securely holding the Foot, and also checked that all the Base clamps were torqued down to the Pier.  The Support Bracket here was then removed (note, this one only has the vertical slot modifications, not the cut out on the top of the Baseplate).

The SW Support Bracket was removed and handed over to Bubba for mods, and the NE one was installed at the SW corner.  Vertical Dial Indicators were installed at these two corners to monitor changes.

Once again, we hoisted the HEPI Assy up onto the Pier and we cleared the interference on top, but just as we were getting ready to drop bolts into the Foot on top, we discovered ANOTHER INTERFERENCE!  This time the base of the HEPI Assy ran into the top of the Bottom Plate of the Support Bracket (see photo).  {Crap!}

Greg then checked the position of the Foot just to confirm we didn't make a mistake with pre-positioning of the Foot (we were a little off and in a way which helped us, but still off).  So we now need to wait until we get a fully modified Support Bracket before we can continue anything at BSC7.

Bottom Clamps & Bent Bolts

At one point it was noticed that non-called out bolts were used for Bottom Clamps (see photo #3) for the NW & SE HEPIs.  As these Clamps were loosened up and the bolts were swapped it was noticed that it was hard to remove some of the bolts.  In fact, there was one bolt which was noticeably bent!  (see photo #2)

Looks like the bend in the bolt occurs at the interface between the bottom of the Bottom Clamp & the top of the Pier.  Apparently the 1/2"-20 set screws and the 35ft-lbs we'd been taking them too is just too much for the 1/2"-13 bolts here.  Unless someone else chimes in we will do the following in the future: 

-Torque 1/2"-13 bolt to 67ft-lbs

-Torque top 1/2"-20 set screws to 25ft-lbs

-Tighten the side 1/2"-20 set screws enough so they won't loosen up on their own.

For what its worth the stainless 1/2"-13 bolts were swapped out with the black HoloKrome bolts.  (Need to do this bolt swap on the SE HEPI, too).

Images attached to this report
H2 General
david.barker@LIGO.ORG - posted 15:12, Friday 25 March 2011 (663)
epics alarms reworked

I cleaned up the vacuum alarm handler to remove those ion pump channels which are always in alarm. All vacuum alarms from now onwards should be treated as real alarms, and hopefull they will be infrequent. I also added the cyropump fill valve alarms, if these go off a pump overfill is imminent. New alarms have guidance text attached.

I changed the alarm startup script (called from the medm site map) to only start the relevant alarm handlers (relevant to the status of the IFO and site at this time).

H2 INS
michael.rodruck@LIGO.ORG - posted 18:18, Thursday 24 March 2011 (661)
H2 PSL Installation

Table legs were grouted into place today. We attached fans to them to help them dry.

Images attached to this report
H2 INS
patrick.thomas@LIGO.ORG - posted 15:53, Thursday 24 March 2011 (660)
Ops Day Summary
PSL table legs grouted
Wire brushing in HAM 12
Dirty room moved over new location of HAM 8 to drill mounting holes
Sprague arrived
BSC7 HEPI work
H2 INS
corey.gray@LIGO.ORG - posted 15:50, Thursday 24 March 2011 (659)
BSC7 NW & SE HEPI Installation Progress

[Corey, Greg]

Had another late start today as we had to give up our crane till late morning (If we had the crane to ourselves, I'm sure we could have easily finished installing HEPIs today).

NW Location

Today, we pulled out the NW aLIGO HEPI (S/N 51) and swapped it with one which had a correctly-positioned HEPI Foot.  As with the SE, this one dropped in nicely and required no horizontal positioning of the Housing (preserving the HEPI Foot range).  As for vertical position, we went with a 0.25" Shim & had to drop the HEPI Foot slightly to accomodate.

Note:  This one is missing a "Right" Housing Clamp.  We have one ready to go and will install it tomorrow.

SW Location

Here we had a iLIGO Actuation Stack in place.  This was removed and staged for "trash/recycling".  The iLIGO Adapter Plate was traced on the Pier.  But for the Drill Template, instead of lining up to the Adapter Plate mark, we set the Template to the (4)-corner Holes on top of the Pier.  Greg then drilled and tapped the holes.  I gathered up clamping hardware.

This HEPI (which will be S/N 77) will be installed in the morning to minimal fanfare.

Images attached to this report
X1 SUS
betsy.weaver@LIGO.ORG - posted 13:15, Thursday 24 March 2011 (658)
Q3 Build and Q2 Re-Build update
Q3 - The final ECD blocks were added to the Main Chain.  TFs were taken before and after the ECD blocks were installed, for comparisons.  We currently do not have a spec on where to set the ECD blocks, so we'll need someone to look at the plots to discuss.  Unfortunately, there is a problem with DTT's ability to re-display saved REF traces in saved files, so I don't have good plots to upload here.  Jim Batch is looking into this problem which apparenly has been a problem in the controlroom as well.

Q2 has been re-hung in the LSAT, refitted as an ITM with weights as per the following:

PenRe = 59,289 g
TCP dummy = 20,032 g
PEN = 39,710 +/-20 g
TM = 39,610 +/- 20 g

The blades of the UIM and Top Masses had been reset to the new lower blade tip parameter set on the bench, so the hang from the UIM down on the LSAT was quite easy - very minimal adjustments made to the blade tip heights and lateral positions.
H2 INS
corey.gray@LIGO.ORG - posted 17:10, Wednesday 23 March 2011 (654)
Today's HEPI Work

(Corey, Greg)

BSC7 NE, SE, & NW HEPI Installation Progress

After consulting with Hugh about NE HEPI work from yesterday, we figured out torque values to work with (1/2" bolts we took to 67ft-lbs & set screws for the base clamps we took to only 35ft-lbs).  We also decided to put (3) thick washers under the two Crossbeam->HEPI Foot bolts which interfered with the HEPI Foot vertical Adjustment Screws.  (Attached is a photo of these bolts---their heads are seen inside the Crossbeam).

In the afternoon, we moved onto doing a full swap at the SE location.  The original HEPI was removed, and then a new one was craned up (this one had a correctly pre-positioned Foot).  The Foot was mated up with the Crossbeam (basically make sure the four bolts on top fit through holes). 

This swap was smooth in a few ways. For Vertical, we were very close to having a 0.25" gap.  So we used the 0.25" Shim and only had to lower the Foot very slightly.  The Foot was then torqued to the Crossbeam.  At this point we checked horizontal positioning of the Assembly (yesterday, the Assembly was slightly off so we had to move the HEPI Housing structure).  Today, our holes lined up, so we didn't have to make any horizontal moves (thus preserving HEPI Foot range---a good thing!).

The HEPI Assy which was installed here (South East) was S/N 45.

We are now staged to do a HEPI swap on the NW Pier in the morning.

HAM HEPI Foot Positioning

We moved to Foot Positioning in the morning since the WEST crane was tied up for most of the morning (HAM12 doors).  Two HEPI Feet were positioned.

Photo Captions:
1)  This is a peak inside the Crossbeam where the heads of the bolts which connect to the HEPI Foot are (notice that two needed several washers as spacers to keep the bolts off of the Vertical Adjustment screws of the HEPI which are below)
2)  The 0.25" Shim installed (and a shot of the Vertical Adjustment screw mentioned above)
3)  Gap between HEPI Housing & Support Bracket (better than yesterday!); this is one of our on-the-fly Support Brackets which was modified by Apollo
Images attached to this report
H2 General
jeffrey.garcia@LIGO.ORG - posted 16:02, Wednesday 23 March 2011 (657)
Ops Day Summary


			
			
H2 General
jeffrey.garcia@LIGO.ORG - posted 16:02, Wednesday 23 March 2011 (656)
Ops Day Summary
Throughout the day:
HEPI install work on BSC7
scrub cleaning prep on HAM 12 – door removed first

~10:15 – contractor on-site for End-Y work

~4:30 – Grant and Robert out to LVEA to crane mounting on the H1 PSL for the squeezer work.

Other:
Dani and Richard modified the Card Access control so the readers will allow exiting doors without an exit swipe.  The enter swipe is still active.  This will reduce alarms in the control room, allow contractors and others to leave and enter without being “locked out”, and not pose any hazards, because  the LVEA is “laser safe”.  

LHO FMCS
kyle.ryan@LIGO.ORG - posted 15:26, Wednesday 23 March 2011 (655)
CP8 follow-up
I closed the check-valve bypass valve for CP8 this morning and enabled the instrument air to the LLCV.  The PID is back in control of CP8's LN2 level.