Adding CHETA slow controls channels to DAQ EDC
Jonathan, Erik, Dave:
Following the installation of the CHETA Beckhoff chassis in the Vacuum Prep Lab we added the 724 AWC channels for itm[x,y] to H1EPICS_ECATTCSCS.ini for inclusion into the EDC.
at 12:22 I did a DAQ 1-leg and EDC restart. The EDC would not run, its systemd service was in a continual respawn state.
The number of EDC channels had increased from 59894 to 60618, and I remembered that there is a channel limit in the EDC code, which Erik verified was 60k.
Erik quickly built a new EDC with a 70k limit and installed this on h1susauxh56.
In the mean time I had put the H1EDC.ini file back and restarted 1-leg and EDC to get everything stable again.
At 13:22 we did a second round of DAQ+EDC restarts with the expanded channel list which was successful.
Installing h1sush6 IO Chassis
Fil, Dave, Erik:
I relocated the old h1sush2b IO Chassis from the CER to the MER. It is in the bottom of the SUS-HAM6 rack, at the same height as the neigboring h1sush7 and h1seih7.
I pulled a new MTP fiber from the IO Chassis to the MER patch panel, using the third port.
This IO Chassis currently has the cards left over after the h1sush2[a,b] consolidation in Dec 2025, we will populate it with the correct cards later.
Current layout:
| A1-1 | LIGO Timing Card | A3-1 | ||
| A1-2 | A3-2 | |||
| A1-3 | A3-3 | |||
| A1-4 | ADC-0 | A3-4 | ||
| A2-1 | 16bit-DAC-0 | A4-1 | Contec6464 BIO-0 | |
| A2-2 | 16bit-DAC-1 | A4-2 | ||
| A2-3 | A4-3 | |||
| A2-4 | A4-4 |
No work was done on the front end computer in the MSR.
Later this week when the IO Chassis is powered up we will make the following changes in the MSR to the old h1susb2b computer:
1. disconnect the Dolphin cable from its IX card and verify the Dolphin switch port is fenced
2. move the MTP from the CER patch over to the 3rd port on the MER patch
3. run puppet to reconfigure the boot server to boot this computer as h1sush6 sans-Dolphin and only running h1iopsush5 model
4. boot the computer and verify the IO Chassis can be seen, the IOP runs and that the timing is good.
h1susb123 accumulated 4 DAQ CRC errors on the 1-leg overnight as reported by DC1, but none on the 0-leg.
| Tue 20:41 PDT | 1 |
| Tue 22:06 PDT | 2 |
| Wed 05:04 PDT | 1 |
| total as of 07:30 Wed | 4 |
All 4 models on h1susb13 increment their CRC counters at the same time. Normally we have zero CRC errors for weeks/months across the board.
I have cleared the CRCs and we will see if this trend continues.
2 more, Wed 14:51 and Thursday 06:15
TITLE: 02/25 Day Shift: 1530-0030 UTC (0730-1630 PST), all times posted in UTC
STATE of H1: Planned Engineering
OUTGOING OPERATOR: None
CURRENT ENVIRONMENT:
SEI_ENV state: MAINTENANCE
Wind: 9mph Gusts, 6mph 3min avg
Primary useism: 0.01 μm/s
Secondary useism: 0.19 μm/s
QUICK SUMMARY:
More JAC work today
The annulus ion pump body for the BSC1 annulus system was replaced. We then hooked up and started the turbo/aux. cart. Pressure at the cart was dropping nicely as pumping commenced.
There will be a pump cart running on the south side of the Y-arm beamtube, near the TCSY table, until the ion pump transition pressure.
The annulus ion pump controller was turned on first thing this morning, and after a few hours the ion pump was able to maintain the pressure of the annulus system. That allowed us to close the isolation valve. After lunch the aux cart and can turbo were removed from the annulus system.
S. Muusse, C. Compton, G. Vajente
We are still in the process of testing the CHETA electronics integration and have began fixing the optical setup on the ITMY Table to test the sensor in situ.
The optical system was realigned with the lenses, waveplate and polariser repositioned to ensure lower 4.65um intensity on the pickoff to prevent burning after the issues in post. All core optics for the 4.65um beam have been placed and we are in the process of adding the sensor paths and laser dumps.
Electronics:
We tested all the laser diode and TEC controller ports on the chassis which were working. It is worth noting when connected to the Laser Enable control the diode will not turn on unless this is enabled and can be used to shut off the laser power.
The thermal power meter input was also working and power changes can be seen on ndscope
I've put in a table the status of all the CDS I/O we've tested so far:
| Sensor | Status | Channel |
| Thermal Power Meter Voltage | Operational | H1:AWC-ITM(OPTIC)_PD_C_VOLTS |
| Laser Enable | Operational | H1:AWC-ITM(OPTIC)_LASER_ENABLE |
| Laser current | Operational | H1:AWC-ITM(OPTIC)_LASER_DIODECURRENTMONITOR |
| Laser Temperature monitor | Operational but uncalibrated | H1:AWC-ITM(OPTIC)_LASER_DIODETEMPMONITOR |
| Flipper | Operational but not installed | H1:AWC-ITM(OPTIC)_FLIPPER_1 |
| Rotation stage | Not operational | H1:AWC-ITM(OPTIC)_POWER |
Some notes are that:
PD_C is the thermal powermeter
PD_A and PD_B are the PDs
We aim to installl the PD setup tomorrow and test its electronics.
Medm
Adjacently, there was continued progress on the medm, a flipper control was installed using SQZT7 code, the slow PD was added using LSC_CUST_DCPD.adl and QPD using QPD.adl. Both will be tested in the coming days on the actual system and the rest of the controls added.
J. Freed (with help from Marc and Fil)
I tested the real wiring chain described in D2400111 from PD through the 3 variants of the TIA and it does follow exactly what is described in the link. There were 4 things of note that were found during this test.
1. All the whitening filters were switched "on" inside the TIA, however our final design document states that only the QPDs need whitening. As such the SPD boards S2500647 and S2500645 whitening switches were set to bypass. I logged this change in the E-Traveler.
2. The D1700116 silicone circuit board for the FFD-200 causes shorts. The main issue is the GAP 5000 pinholes on the PD side of the board. If the PD is flush with the board those pins touch the case of the FFD. Since the GAP pins are also connected to the cathode and anode, this causes the circuit to short. This is simple enough to test without taking out any PDs from the case. If there is "no" resistance between the case (ground) pin and the anode/cathode pins on the DB9 connector coming from the PD, then it is shorting and the system should not be turned on. There are 2 options suggested to fix this, either put insolation between the GAP pins and the FFD case or cut the GAP pins connection to the FFD anode/cathode. For this specific test, the issue was bypassed by putting in a tissue between the FFD and the silicone board.
3. I tried to take transfer functions from all the PDs through the TIA, however the laser I used (the MIT ISC AM Laser) AM modulation was designed for 5 - 200 MHz, not the 4096Hz we are trying to use. As such, I suspect the harsh attenuation (~70dB at 4096Hz AOM_Attinuation.png) I measured was caused by the laser. So I decided it would be better to put off the transfer functions through the TIA until after SPI is built, then use our own laser AOM system to run the test. The laser was just left at DC and was used as the light source to see if signals on the PDs follow the correct wiring chain.
4. I used the laser to check that the signals on the PDs follow the expected wiring chain through the output of the TIA. Ex. Laser on Quadrent 1 of the QPD outputs a voltage on the expected pin on the output of the TIA. All pins were found to be correct.
We checked the production units, and they do NOT suffer from the shorts described in item 2 above. *phew* Great work Dean! See details in LHO:89263.
Jason, Jennie, Betsy After working for a bit to try to beam dump the second Septum refl beam dump which also is coming off the IMC septum window, we finally came to a solution. It involved stealing one of the SPI D1800140-07 smallest beam dump panels and also putting it into the same mount as the first panel. These 2 beams are pretty close to the main beam at this location, but with the beams otherwise hitting the internal metal of the output periscope we could not come up with anything better. It took us quite a few small adjustments and many pictures to convince ourselves we are not clipping, but the attached picture is the best visual of the situation. Commissioners agree that this is what we will live with.
TITLE: 02/25 Day Shift: 1530-0030 UTC (0730-1630 PST), all times posted in UTC
STATE of H1: Planned Engineering
INCOMING OPERATOR: N/A
SHIFT SUMMARY: Another productive day working towards closing out HAM1.
LOG:
| Start Time | System | Name | Location | Lazer_Haz | Task | Time End |
|---|---|---|---|---|---|---|
| 22:49 | SAF | LVEA is Laser SAFE | LVEA | NO* | LVEA is Laser SAFE *Bifurcated HAM1/2* | Ongoing |
| 15:42 | FAC | Kim, Nellie | LVEA | N | Technical cleaning | 16:09 |
| 15:47 | FAC | Eric | Site | N | Running fire pumps | 16:22 |
| 15:55 | FAC | Tyler, cont. | EY | N | Groundwater sampling | 16:17 |
| 16:36 | SPI | Jeff | Opt Lab | Local | SPI characterization | 22:39 |
| 16:36 | CDS | Fil | LVEA | N | HAM5 electronics rack work | 21:16 |
| 16:37 | TCS | Camilla | Opt Lab | N | Inspecting viewports | 18:00 |
| 16:41 | FAC | Kim | LVEA | N | Technical cleaning | 17:24 |
| 16:54 | OPS | Gabriele +2 | LVEA | N | Tour | 17:50 |
| 17:23 | JAC | Betsy | LVEA | YES | Adjusting covers | 17:44 |
| 17:24 | VAC | Travis | LVEA | n | Checking on GV6 | 17:34 |
| 17:25 | JAC | Sheila | LVEA | YES | Opening light pipe | 17:40 |
| 17:25 | FAC | Randy | LVEA | N | Walkabout in W-bay | 17:41 |
| 18:06 | FAC | Randy | LVEA | - | Changing out cleanroom bolts (craning at height) | 20:33 |
| 18:09 | CAL | Oli | PCal Lab | N | Checking spare lasers | 18:25 |
| 18:16 | CDS | Marc | LVEA | N | HAM3 electronics rack work | 21:16 |
| 18:36 | SUS | Oli | MER | N | Checking SUS racks | 18:44 |
| 18:37 | VAC | Jordan | LVEA | N | Opening HAM7 ion pump | 19:09 |
| 19:03 | VAC | Travis | LVEA | - | Checking HAM1 feedthrus | 19:08 |
| 19:13 | JAC | Jason | LVEA | Yes | HAM1 beam hunting | 20:55 |
| 19:20 | JAC | Jennie | LVEA | Yes | HAM1 beam hunting | 20:56 |
| 19:48 | TCS | Sophie | Prep Lab | N | Hunting for screws | 19:54 |
| 20:28 | JAC | Sheila | LVEA | Yes | Delivering keys, centering IMC WFS | 20:58 |
| 20:33 | FAC | Randy | LVEA | - | Craning to replace cleanroom bolts | 22:24 |
| 21:19 | VAC | Jordan | LVEA | N | Setting up BSC1 AIP swap | 21:44 |
| 21:33 | IOO | Sheila | LVEA | N | Centering IMC WFS | 21:44 |
| 21:33 | JAC | Keita | LVEA | Yes | HAM1 alignment | 21:44 |
| 21:42 | TCS | Sophie | Prep Lab | Local | CHETA table work | Ongoing |
| 22:06 | TCS | Camilla | Prep Lab | Local | CHETA table work | Ongoing |
| 22:17 | VAC | Gerardo, Jordan | LVEA | - | AIP replacement on BSC1 | Ongoing |
| 22:28 | VAC | Travis | LVEA | N | Disconnect GV6 pump cart | 01:08 |
| 22:29 | JAC | Jason, Jennie, Betsy | LVEA | Yes | HAM1 cleanup; Betsy out @ 00:17 | 00:28 |
| 22:29 | AOS | Sheila, Shreyan, Bin | LVEA | - | Looking around at HAM1 | 22:58 |
| 22:34 | SUS | Oli | LVEA | N | Verify existence of a sat amp | 22:43 |
| 22:41 | SUS | Dave | MER | N | SUS rack work | Ongoing |
| 23:12 | SUS | Oli | CER | N | Looking at a chassis | 23:16 |
| 23:25 | SUS | Oli | CER | N | Looking at a different chassis | 23:29 |
Alignment into HAM2
Locked JAC with RF at 1W. IMC WFS was centered in IOT2L and IMC started working. As we steered JM3 MC2 TRANS responded as expected (i.e. JM3 PIT -> MC2 YAW and vice versa though there's a significant cross coupling). Sheila had to recenter the WFS once again at some point as the WFS started to get off-centered as we turned JM3, but as far as the WFSs were centered, things worked.
In the end, MC2 TRANS was centered reasonably well (right before the cursor in the attached), JM3 DAC output was O(1e7) while a 28 bit DAC's range is +-134e6.
Apparently we made the last step of JM3 PIT adjustment in the wrong direction at the time (we didn't notice because the WFS is very slow) and overshot. I steered it back later, now H1:SUS-JM3_M1_OPTICALIGN_P_OFFSET is -39 instead of -19 (second screen shot).
Anyway, this means that the alignment into HAM2 is good with more than a comfortable range left for JM3. No need to further refine.
One caveat is that the IM4 trans is totally off in PIT. But that's a downstream problem which we'll have to deal with later in HAM2. That should not prevent us from moving forward to close down the chamber.
The tasks listed below are described in different alogs.
JAC TRANS PD calibration
Last beam dump (alog 89249)
ALS beam path check
Summary: JAC TRANS PD well aligned, rough power budget done, ALS beam from PSL does not hit any wires or components before reaching its intended steering mirror in HAM1.
POWER BUDGET
Jason and I went into do some measurements on the TRANS PD path after 11am. We were unsure yesterday that this PD was well aligned after the laser window installation.
The beam going to the TRANS PD matches roughly what we expect with the uncoated laser window we now have as BS1. Here is a photo showing the power Keita and Jason were getting after swapping in the laser from yesterday (in the lower left plot).
There was approx 0.03 on TRANS PD. Previously with a HR mirror in place of BS1 we had ~ 3 on TRANS PD (see lower left plot on ndscope).
Keita did a calculation of the rough power reflected from BS1, assuming an AOI of both 40 degrees or 35 degrees (AOI should be around 39 degrees according to layout).
rp=tan(theta-phi)/tan(theta+phi)
theta is the AOI and phi is the angle of refraction,
phi = asin(sin(theta)/n),
n=1.4496 for fused silica at 1064nm.
rp(theta=40deg)^2 = 1.14%
rp(theta=35deg)^2 = 1.63%
This means that the beam is likely not clipping on the TRANS PD as the power on it seems to have scaled as we expect with the laser window installation.
To double check this and provide a calibration for this PD we did some power meter measurements in chamber.
We measured the output from the input side curved mirror of the JAC (Te2), with the PSL set to 1W output using the rotation stage (otherwise it is hard to see this beam on the card).
JAC Te2 = 2.7 mW
JACT_BS1 transmitted beam = 2.4 mW
JAC TRANS PD beam = 37 microW
This leaves us with 0.263 mW unaccounted for in transmission, this puzzles me.
We put the power out of the PSL down to 100 mW to measure the input power and output power in HAM1.
JAC input power = 115 mW
HAM2 input power/after HAM1 output periscope= 96mW
ALS BEAM CHECK
Jason opened the light pipe and checked that beam does not intersect anything int he new installed path before reaching its SM that directs it towards ISCT1.
It seems that whitening gains of some corner station QPDs were somehow set to zero on Friday Feb/20 17:22 UTC (09:22 PST).
Not sure why this happened, this seems to be earlier than the failed effort to update h1imcasc model (alog 89208). ALS QPDs, end station QPDs and all WFS RFs are good. Was something done to Beckhoff that day?
I first noticed this for MC2 trans yesterday because it was interfering with IMC locking and WFS triggering. I checked all QPDs and WFS today and found that the following channels were affected. I restored them all to the value right before it was set to zero.
| channel | old (dB) | new (dB) |
| H1:IMC-MC2_TRANS_WHITEN_GAIN | 0 | 30 |
| H1:IMC-IM4_TRANS_WHITEN_GAIN | 0 | 18 |
| H1:ASC-AS_C_WHITEN_GAIN | 0 | 18 |
| H1:ASC-OMC_A_WHITEN_GAIN | 0 | 27 |
| H1:ASC-OMC_B_WHITEN_GAIN | 0 | 27 |
Trending the uptime of the Ethercat system, slow controls were restarted and came back up two seconds before the time listed in Keita's alog, likely a part of Daniel's updates to include CHETAX electronics (alog89211). Settings may just have not been fully recovered after that restart.
Tue Feb 24 10:14:58 2026 INFO: Fill completed in 14min 54secs
Bypass will expire:
Tue Feb 24 11:57:58 AM PST 2026
For channel(s):
H0:FMC-CS_FIRE_PUMP_1
H0:FMC-CS_FIRE_PUMP_2
TITLE: 02/24 Day Shift: 1530-0030 UTC (0730-1630 PST), all times posted in UTC
STATE of H1: Planned Engineering
OUTGOING OPERATOR: None
CURRENT ENVIRONMENT:
SEI_ENV state: MAINTENANCE
Wind: 3mph Gusts, 1mph 3min avg
Primary useism: 0.03 μm/s
Secondary useism: 0.29 μm/s
QUICK SUMMARY: In the homestretch on HAM1 alignment activities and JAC commissioning, which continues on this rainy morning.
The IMC_LOCK Guardian had been left trying to acquire all night with the light pipe closed, so I set it back to DOWN when I noticed that this morning.
Workstations were updated and rebooted. This was an OS packages update. Conda packages were not updated.
02/23 S. Muusse, C. Compton, G. Vajente, S.Goswami, B. Wu
The electronics chassis was brought into the lab today (thanks Phil and Dave) and we began testing the integration of the optomechanics with the CDS. An ethernet cable was run into the JOAT CHETA lab to connect to the server. A variable power supply was brought into the lab to power the chassis at the required 24V along with a linear power supply required for the rotation stage and translation stages.
The flipper I/O input and output had to be configured for Beckhoff communications using this guide.
The current status of our testing is as follows:
Working:
Not working:
Untested:
We have realised during this process that the flipper isn't powered by the SMA connectors and requires a seperate power source. This was not considered in the initial panel design and is not currently supplied by the chassis. There is a spare blank connector input/output slot which can be used.
We have begun making the medm display for the CHETA system based on the current CO2 medm which shares many optomechanical systems. CHETA isn't currently on the TCS screen so to run the medm display currently the following command must be run to access the work in progress.
medm -x -macro 'USERAPPS=/opt/rtcds/userapps/release/,SITE=LHO,site=lho,IFO=H1,ifo=h1,OPTIC=X,OPTICF=ITMX,name=AWCITMX,RT_MEDM=/opt/rtcds/lho/h1/medm' TCS_CHETA.adl
To open the medm in a configurable format:
medm TCS_CHETA.adl
Alternatively to edit the code files:
code medm TCS_CHETA.adl
Further alignment on the ITMY table was completed with almost all optics now mounted on the table.
We installed JM1, balanced it and aligned it. A beam dump was placed behind it though we could not see the transmission with 1W input.
After this, JAC locked with RF without any problem though the input was wobbly when the purge was up.
We searched for unexpected ghost beams (also with 1W input) and didn't find any.
We uninstalled many (but not all) temporary dog clamps and irises.
We revisited the IMC alignment because it's been off in PIT since Thursday or Friday. We locked JAC using dither (because we wanted to turn down the purge air). We enabled the IMC WFS just for MC optics and steered JM3, but weren't able to center the MC2 trans. Steering JM3 just made the IMC transmission worse while making not much impact on the desired degree of freedon (JM3 PIT -> MC2 trans YAW, JAM3 YAW -> MC2 trans PIT).
Tomorrow, we'll revisit the IMC alignment. We'll also measure the power coming into JAC TRANS PD as well as the actual transmission of JAC while locking it with RF so we can use JAC trans PD as the measure of the power into HAM1.
FYI, there are about 24 beam dumps now installed on this table.
Tagging for EPO photos
One of the beam dumps on the picture was most likely NOT in its final place.
See my annotated version, the BD circled in orange is probably JM1 trans beam dump and relocated to the final location after this picture was shot.
In Feb/26 alog, this picture of Betsy's doesn't show the mystery dump and instead shows the JM1 trans beam dump in its final location, I think.
Today, Gerardo replaced the annulus ion pump body for the GV6 annulus system. He then handed off to me to hook up the turbo/aux. cart. The pressure at the cart was ~3e-5 after 4 hours of pumping.
There will be a pump cart running at GV6, at the Y-arm termination slab, until the ion pump transition pressure.
Transitioned to ion pump successfully. Aux cart and turbo were removed.
Tue24Feb2026
LOC TIME HOSTNAME MODEL/REBOOT
12:22:50 h1daqdc1 [DAQ] <<< First try of 1-leg + EDC restart
12:23:00 h1daqfw1 [DAQ]
12:23:01 h1daqtw1 [DAQ]
12:23:04 h1daqnds1 [DAQ]
12:23:09 h1daqgds1 [DAQ]
12:27:09 h1daqgds1 [DAQ] (GDS1 needed a restart)
12:27:39 h1susauxh56 ***REBOOT*** <<< EDC wont start, tried a reboot
12:28:38 h1susauxh56 h1iopsusauxh56
12:28:51 h1susauxh56 h1susauxh56
12:33:33 h1susauxh56 h1edc[DAQ] <<< backed out EDC chan change, restarted EDC+1-leg
12:34:32 h1daqdc1 [DAQ]
12:34:44 h1daqfw1 [DAQ]
12:34:44 h1daqtw1 [DAQ]
12:34:45 h1daqnds1 [DAQ]
12:34:52 h1daqgds1 [DAQ]
12:35:32 h1daqgds1 [DAQ] (GDS1 needed a restart)
13:22:31 h1daqdc1 [DAQ] <<< Restart 1-leg + EDC with new code and new chans
13:22:44 h1daqfw1 [DAQ]
13:22:45 h1daqtw1 [DAQ]
13:22:48 h1daqnds1 [DAQ]
13:22:54 h1daqgds1 [DAQ]
13:24:13 h1susauxh56 h1edc[DAQ]
13:31:12 h1daqgds0 [DAQ] <<< Restart 0-leg
13:31:19 h1daqfw0 [DAQ]
13:31:19 h1daqtw0 [DAQ]
13:31:20 h1daqnds0 [DAQ]
13:31:40 h1daqfw1 [DAQ] <<< FW1 spontaneous restart